Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
111
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Phase Rotation Error
Unit input phase sequence is not A, B, C. The phase sequence should be verified 
and corrected.
Subfeed Current Ix Crest Factor
Subfeed breaker phase X Current Crest Factor (peak/RMS).
Subfeed Current Ix THD
Current Total Harmonic Distortion for Subfeed breaker phase X.
Subfeed Current Ix
Subfeed breaker RMS current for phase X.
Subfeed Current Iy Crest Factor
Subfeed breaker phase Y Current Crest Factor (peak/RMS).
Subfeed Current Iy THD
Current Total Harmonic Distortion for Subfeed breaker phase Y.
Subfeed Current Iy
Subfeed breaker RMS current for phase Y.
Subfeed Current Iz Crest Factor
Subfeed breaker phase Z Current Crest Factor (peak/RMS).
Subfeed Current Iz THD
Current Total Harmonic Distortion for Subfeed breaker phase Z.
Subfeed Current Iz
Subfeed breaker RMS current for phase Z.
Subfeed Ground Current
Subfeed breaker Ground RMS current.
Subfeed Ground Overcurrent
Subfeed breaker Ground current has exceeded the limit.
Subfeed Neutral Current
Subfeed breaker Neutral RMS current.
Subfeed Neutral Overcurrent
Subfeed breaker Neutral current has exceeded the limit.
Subfeed Output kW-Hrs
Subfeed breaker accumulated KW-Hours since last KW-Hours reset.
Subfeed Output Percent Load
Subfeed breaker percent load of rated current
Subfeed Output Power (kVA)
Subfeed breaker output kVA.
Subfeed Output Power (kW)
Subfeed breaker output KW
Subfeed Phase Overcurrent
Subfeed breaker phase current has exceeded the limit.
Subfeed Power Factor
Subfeed breaker Power Factor (real power/apparent power)
System Date and Time
Unit date and time
System Event Acknowledge/Reset
Alarm Present/Reset
System Shutdown - EPO
Unit shutdown by Emergency Power Off (EPO) switch
System Shutdown - REPO
Unit shutdown by Remote Emergency Power Off (REPO) switch
System Status
The operating status for the system
Transformer Overtemperature Power 
Off
Output power shutdown due to high transformer temperature
Transformer Overtemperature 
Shutdown
Unit shutdown due to transformer over temperature
Transformer Overtemperature
Transformer temperature has exceeded the limit
Transformer Overtemperature
Transformer temperature has exceeded the limit
Transformer Temperature Sensor Fail
Transformer temperature sensor has failed
Table 37
Liebert FDC
, Liebert FPC
, Liebert RDC
, Liebert RX
 - Glossary (continued)
Data Label
Data Description