Emerson MODBUS IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
146
Output
Source
—
40050
1
—
1 = Other
2 = None
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
Frequency
—
40051
1
10
Units: Hz
Number Lines
—
40052
1
—
—
Voltage L1
—
40053
1
—
Units: V
Voltage L2
—
40054
1
—
Units: V
Voltage L3
—
40055
1
—
Units: V
Current L1
—
40056
1
10
Units: A
Current L2
—
40057
1
10
Units: A
Current L3
—
40058
1
10
Units: A
Real Power L1
—
40059
1
10
Units: kW
Real Power L2
—
40060
1
10
Units: kW
Real Power L3
—
40061
1
10
Units: kW
Percent Load L1
—
40062
1
—
Units: %
Percent Load L2
—
40063
1
—
Units: %
Percent Load L3
—
40064
1
—
Units: %
Bypass
Line Bads
Line Bads
—
40070
1
—
—
Frequency
—
40071
1
10
Units: Hz
Number Lines
—
40072
1
—
—
Voltage L1
—
40073
1
—
Units: V
Voltage L2
—
40074
1
—
Units: V
Voltage L3
—
40075
1
—
Units: V
Current L1
—
40076
1
10
Units: A
Current L2
—
40077
1
10
Units: A
Current L3
—
40078
1
10
Units: A
Alarms
Alarms Present
Alarms Present
—
40087
1
—
Bit 0
On Battery
—
40087
1
—
Bit 2
Low Battery
—
40087
1
—
Bit 3
Depleted Battery
—
40087
1
—
Bit 4
Temperature Bad
—
40087
1
—
Bit 5
Input Bad
—
40087
1
—
Bit 6
Output Overload
—
40088
1
—
Bit 0
On Bypass
—
40088
1
—
Bit 1
Bypass Bad
—
40088
1
—
Bit 2
Charger Failed
—
40088
1
—
Bit 5
Fan Failure
—
40089
1
—
Bit 0
General Fault
—
40089
1
—
Bit 2
Table 54
Liebert NX 225-600kVA UPS - Input and Holding
3
(continued)
Data Description
Input
Holding
Register
# of
Reg
Scale
Notes/Units