Emerson MODBUS IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - UPS Systems
149
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Battery Over Temperature
10350
—
1
Active on Warning
N+1, 1+N, 1+1, SMS
DC Bus Ground Fault - Positive
10351
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
DC Bus Ground Fault - Negative
10352
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Output Low Power Factor
10353
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Leading Power Factor
10354
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Output Amp Over User Limit-Phs A
10355
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Output Amp Over User Limit-Phs B
10356
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Output Amp Over User Limit-Phs C
10357
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Output Fault
10358
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Overload Phase A
10359
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Overload Phase B
10360
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Overload Phase C
10361
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Inhibit - External
10362
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Shutdown - Overload
10363
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Off - External
10364
—
1
Active on Alarm
CE only
Inverter Static Switch SCR Short
10365
—
1
Active on Alarm
CE only
Equipment Over Temperature
10366
—
1
Active on Warning
SCC, N+1, 1+N, 1+1, SMS
Equipment Over Temperature
10367
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Equipment Temperature Sensor Fail
10368
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 01
10369
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 02
10370
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 03
10371
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 04
10372
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 05
10373
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 06
10374
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 07
10375
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 08
10376
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 09
10377
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 10
10378
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 11
10379
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 12
10380
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 13
10381
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 14
10382
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 15
10383
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 16
10384
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Rectifier Operation Inhibit-Ext
10385
—
1
Active on Alarm
Deprecated
System Fan Failure - Redundant
10386
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Multiple Fan Failure
10387
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Auto Restart In Progress
10388
—
1
Active on Alarm
SCC, SMS
Automatic Restart Failed
10389
—
1
Active on Alarm
SCC, SMS
Fuse Failure
10390
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
System Breaker(s) Open Failure
10391
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
System Breaker(s) Close Failure
10392
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Filter Cycle Lock
10393
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Service Code Active
10394
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
LBS Inhibited
10396
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Table 55
Liebert NXL
™
- 60Hz, UL version (Model 40) - Status and Coil (continued)
Data Label
Status
Coil
# of Bits
Notes
NXL Type