Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
200
Table 70
Liebert Series 610 SCC UPS - Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines
30004
40004
1
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
Bits 4 - 7
Number of Output Lines
30004
40004
1
Bits 8 - 11
Nominal Power Rating
30021
40021
2
VA
Nominal Input Voltage
30027
40027
1
V
Nominal Output Voltage
30028
40028
1
V
Nominal Static Bypass Switch Voltage
30029
40029
1
V
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
-
Silence Alarm
40101
1
-
Load (Apparent Power)
30102
2
VA
Load (Real Power)
30104
2
W
Load / Capacity
30106
1
%
Output Frequency
30108
1
10
Hz
Bypass Frequency
30109
1
10
Hz
Input Voltage L1
30153
1
V
Bypass Voltage L1
30159
1
V
Bypass Current L1
30160
1
A
Output Voltage L1
30163
1
V
Output Current L1
30164
1
A
Input Voltage L2
30203
1
V
Bypass Voltage L2
30209
1
V
Bypass Current L2
30210
1
A
Output Voltage L2
30213
1
V
Output Current L2
30214
1
A
Input Voltage L3
30253
1
V
Bypass Voltage L3
30259
1
V
Bypass Current L3
30260
1
A
Output Voltage L3
30263
1
V
Output Current L3
30264
1
A
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.