Emerson MODBUS IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
200
Table 70
Liebert Series 610 SCC UPS - Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines
30004
40004
1
—
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
—
Bits 4 - 7
Number of Output Lines
30004
40004
1
—
Bits 8 - 11
Nominal Power Rating
30021
40021
2
—
VA
Nominal Input Voltage
30027
40027
1
—
V
Nominal Output Voltage
30028
40028
1
—
V
Nominal Static Bypass Switch Voltage
30029
40029
1
—
V
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
-
Silence Alarm
—
40101
1
—
-
Load (Apparent Power)
30102
—
2
—
VA
Load (Real Power)
30104
—
2
—
W
Load / Capacity
30106
—
1
—
%
Output Frequency
30108
—
1
10
Hz
Bypass Frequency
30109
—
1
10
Hz
Input Voltage L1
30153
—
1
—
V
Bypass Voltage L1
30159
—
1
—
V
Bypass Current L1
30160
—
1
—
A
Output Voltage L1
30163
—
1
—
V
Output Current L1
30164
—
1
—
A
Input Voltage L2
30203
—
1
—
V
Bypass Voltage L2
30209
—
1
—
V
Bypass Current L2
30210
—
1
—
A
Output Voltage L2
30213
—
1
—
V
Output Current L2
30214
—
1
—
A
Input Voltage L3
30253
—
1
—
V
Bypass Voltage L3
30259
—
1
—
V
Bypass Current L3
30260
—
1
—
A
Output Voltage L3
30263
—
1
—
V
Output Current L3
30264
—
1
—
A
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.