Emerson MODBUS IP Manuel D’Utilisation
![Emerson](https://files.manualsbrain.com/attachments/1ef3aaad462e024fde6cecf537a4c6c781334d44/common/fit/150/50/6dab323528eefa0342baa74a10c15551c3b956250cf9d62f2117dcdf42a7/brand_logo.jpeg)
BACnet Communications - Thermal Management Products
225
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
System Events - iCOM DO Board 3
Digital Output Board Not Detected
Binary_Value
349
5417_1_3
RD
Active on Alarm
1, 2, 3,
4, 5, 6
Remote Sensors
Remote Sensor Average Over
Remote Sensor Average Over
Temperature
Binary_Value
361
5593_1
RD
Active on Alarm
2, 3, 4,
5, 6
Remote Sensor Average Under
Temperature
Binary_Value
362
5594_1
RD
Active on Alarm
2, 3, 4,
5, 6
Remote Sensor System Average Over
Temperature
Binary_Value
363
5595_1
RD
Active on Alarm
2, 3, 4,
5, 6
Remote Sensor System Average
Under Temperature
Binary_Value
364
5596_1
RD
Active on Alarm
2, 3, 4,
5, 6
Remote Sensors - Remote Sensor 1
Remote Sensor Over Temperature
Binary_Value
376
5597_1_1
RD
Active on Alarm
2, 3, 4,
5, 6
Remote Sensor Under Temperature
Binary_Value
377
5598_1_1
RD
Active on Alarm
2, 3, 4,
5, 6
Remote Sensor Issue
Binary_Value
378
5060_1_1
RD
Active on Alarm
1, 2, 3,
4, 5, 6
Remote Sensors - Remote Sensor 2
Remote Sensor Over Temperature
Binary_Value
390
5597_1_2
RD
Active on Alarm
2, 3, 4,
5, 6
Remote Sensor Under Temperature
Binary_Value
391
5598_1_2
RD
Active on Alarm
2, 3, 4,
5, 6
Remote Sensor Issue
Binary_Value
392
5060_1_2
RD
Active on Alarm
2, 3, 4,
5, 6
Remote Sensors - Remote Sensor 10
Remote Sensor Over Temperature
Binary_Value
502
5597_1_10
RD
Active on Alarm
2, 3, 4,
5, 6
Remote Sensor Under Temperature
Binary_Value
503
5598_1_10
RD
Active on Alarm
2, 3, 4,
5, 6
Remote Sensor Issue
Binary_Value
504
5060_1_10
RD
Active on Alarm
2, 3, 4,
5, 6
Remote Sensor Over Temperature
Binary_Value
502
5597_1_10
RD
Active on Alarm
2, 3, 4,
5, 6
Remote Sensor Under Temperature
Binary_Value
503
5598_1_10
RD
Active on Alarm
2, 3, 4,
5, 6
Remote Sensor Issue
Binary_Value
504
5060_1_10
RD
Active on Alarm
2, 3, 4,
5, 6
Air Economizer
Air Economizer Emergency Override
Binary_Value
516
5600_1
RD
Active on Alarm
2, 3, 4,
5, 6
Air Economizer Reduced Airflow
Binary_Value
517
5601_1
RD
Active on Alarm
2, 3, 4,
5, 6
Electronic Expansion Valves
EEV Unspecified General Event
EEV Unspecified General Event
Binary_Value
540
5625_1
RD
Active on Alarm
4, 5
Static Pressure
Static Pressure Sensor Issue
Static Pressure Sensor Issue
Binary_Value
563
5629_1
RD
Active on Alarm
3, 5, 6
High Static Pressure
Binary_Value
564
5630_1
RD
Active on Alarm
3, 5, 6
Table 76
Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Binary Data (continued)
Controller
Liebert iCOM
®
v4
Data Description
Object Type
Instance
Object
Name
Access
Notes
Extra
Notes