Emerson MODBUS IP Manuel D’Utilisation
![Emerson](https://files.manualsbrain.com/attachments/1ef3aaad462e024fde6cecf537a4c6c781334d44/common/fit/150/50/6dab323528eefa0342baa74a10c15551c3b956250cf9d62f2117dcdf42a7/brand_logo.jpeg)
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
228
Return Air Temperature Set
Point
Analog_Value
10032
5333_1_1_deg
_F
RW
Units: deg F
1
Return Air Over Temp Threshold
Analog_Value
33
5022_1_1
RW
Units: deg C
1, 2, 3,
4, 5, 6
Return Air Over Temp Threshold
Analog_Value
10033
5022_1_1_deg
_F
RW
Units: deg F
1, 2, 3,
4, 5, 6
Return Air Under Temp
Threshold
Analog_Value
34
5334_1_1
RW
Units: deg C
1, 2, 3,
4, 5, 6
Return Air Under Temp
Threshold
Analog_Value
10034
5334_1_1_deg
_F
RW
Units: deg F
1, 2, 3,
4, 5, 6
Air - External Sensors
Ext Air Sensor A Temperature
Analog_Value
45
4594_1_1
RD
Units: deg C
1, 2, 3,
4, 5, 6
Ext Air Sensor A Temperature
Analog_Value
10045
4594_1_1_deg
_F
RD
Units: deg F
1, 2, 3,
4, 5, 6
Ext Air Sensor B Temperature
Analog_Value
46
4597_1_1
RD
Units: deg C
1, 2, 3,
4, 5, 6
Ext Air Sensor B Temperature
Analog_Value
10046
4597_1_1_deg
_F
RD
Units: deg F
1, 2, 3,
4, 5, 6
Ext Air Sensor C Temperature
Analog_Value
47
5336_1_1
RD
Units: deg C
1, 2, 3,
4, 5, 6
Ext Air Sensor C Temperature
Analog_Value
10047
5336_1_1_deg
_F
RD
Units: deg F
1, 2, 3,
4, 5, 6
Ext Air Sensor A Over Temp
Threshold
Analog_Value
48
5337_1_1
RW
Units: deg C
1, 2, 3,
4, 5, 6
Ext Air Sensor A Over Temp
Threshold
Analog_Value
10048
5337_1_1_deg
_F
RW
Units: deg F
1, 2, 3,
4, 5, 6
Ext Air Sensor A Under Temp
Threshold
Analog_Value
49
5338_1_1
RW
Units: deg C
1, 2, 3,
4, 5, 6
Ext Air Sensor A Under Temp
Threshold
Analog_Value
10049
5338_1_1_deg
_F
RW
Units: deg F
1, 2, 3,
4, 5, 6
Outside Air Temperature
Analog_Value
50
5574_1_1
RD
Units: deg C
2, 3, 4,
5, 6
Outside Air Temperature
Analog_Value
10050
5574_1_1_deg
_F
RD
Units: deg F
2, 3, 4,
5, 6
Humidity
Return Humidity
Analog_Value
60
5028_1
RD
Units: % RH
1, 2, 3,
4, 5, 6
Humidity Set Point
Analog_Value
61
5029_1
RW
Units: % RH
1, 2, 3,
4, 5, 6
Return Humidity Set Point
Analog_Value
62
5339_1
RW
Units: % RH
1
Humidity Proportional Band
Analog_Value
63
5341_1
RW
Units: % RH
1, 2, 3,
4, 5, 6
Humidity Dead Band
Analog_Value
64
5032_1
RW
Units: % RH
1, 2, 3,
4, 5, 6
Humidity Proportional Control
Integration Time
Analog_Value
65
5342_1
RW
Units: min
1, 2, 3,
4, 5, 6
High Return Humidity Threshold
Analog_Value
66
5033_1
RW
Units: % RH
1, 2, 3,
4, 5, 6
Low Return Humidity Threshold
Analog_Value
67
5035_1
RW
Units: % RH
1, 2, 3,
4, 5, 6
Table 78
Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Analog Data (continued)
Data Label
Object Type
Instanc
e
Object Name
Acces
s
Notes
Extra
Notes