Emerson MODBUS IP Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
258
Unit Partial Shutdown
Binary_Value
237
5112_1
RD
Active on Alarm
Unit Shutdown
Binary_Value
238
5113_1
RD
Active on Alarm
Water Leakage Detector Sensor Issue
Binary_Value
239
5114_1
RD
Active on Alarm
BMS Communications Timeout
Binary_Value
240
5115_1
RD
Active on Alarm
Maintenance Due
Binary_Value
241
5116_1
RD
Active on Alarm
Maintenance Completed
Binary_Value
242
5117_1
RD
Active on Alarm
Clogged Air Filter
Binary_Value
243
5118_1
RD
Active on Alarm
RAM Battery Issue
Binary_Value
244
5119_1
RD
Active on Alarm
Master Unit Communication Lost
Binary_Value
245
5120_1
RD
Active on Alarm
High Power Shutdown
Binary_Value
246
5121_1
RD
Active on Alarm
Supply Fluid Temp Sensor Issue
Binary_Value
247
4651_1
RD
Active on Alarm
GlobalCondenser 
Condenser Outside Air Temp Sensor Issue 
Binary_Value 
259
5535_1 
RD
Active on Alarm
Condenser Outside Air Temp Out of Operating 
Range 
Binary_Value 260
5536_1 RD
Active 
on 
Alarm
Condenser Control Board Issue 
Binary_Value 
261
5537_1 
RD
Active on Alarm
Condenser Refrigerant Pressure Over Threshold Binary_Value 
262
5539_1 
RD
Active 
on 
Alarm
Condenser Refrigerant Pressure Under 
Threshold 
Binary_Value 263
5540_1 RD
Active 
on 
Alarm
Condenser Refrigerant Pressure Sensor Issue 
Binary_Value 
264
5541_1 
RD
Active on Alarm
GlobalCondenser - GC Fan 1
Condenser Fan Issue 
Binary_Value 
280
5277_1_1
RD
Active on Alarm
GlobalCondenser - GC Fan 2
Condenser Fan Issue 
Binary_Value 
292
5277_1_2
RD
Active on Alarm
Table 83
Liebert CRV
 - Binary Data (continued)
Controller Liebert iCOM
®
 v4
Data Label
Object Type
Instance
Object
Name
Access
Notes