306
Table 102 Liebert APS
 - Binary Data
Data Label
Object Type
Instance
Object
Name
Access
Notes
Input
Rectifier Failure 
Binary_Value
1
4295_1
RD
Active on Alarm
System Input Power Problem 
Binary_Value
2
4122_1
RD
Active on Alarm
System Input Current Imbalance 
Binary_Value
3
4382_1
RD
Active on Alarm
Bypass
UPS Output on Bypass 
Binary_Value
14
4298_1
RD
Active on Alarm
Output Load on Maint. Bypass 
Binary_Value
15
4299_1
RD
Active on Alarm
Bypass Not Available 
Binary_Value
16
4135_1
RD
Active on Alarm
Bypass Overload 
Binary_Value
17
5798_1
RD
Active on Alarm
Bypass Frequency Error 
Binary_Value
18
4175_1
RD
Active on Alarm
Bypass Auto Retransfer Failed 
Binary_Value
19
4138_1
RD
Active on Alarm
Battery
Battery Discharging 
Binary_Value
30
4168_1
RD
Active on Alarm
Battery Manual Test In Progress 
Binary_Value
31
4171_1
RD
Active on Alarm
Battery Auto Test In Progress 
Binary_Value
32
4172_1
RD
Active on Alarm
Battery Test Passed 
Binary_Value
33
4322_1
RD
Active on Alarm
Battery Test Failed 
Binary_Value
34
4323_1
RD
Active on Alarm
Low Battery - Shutdown Imminent 
Binary_Value
35
5801_1
RD
Active on Alarm
Battery Module Fault 
Binary_Value
36
5856_1
RD
Active on Alarm
Battery Module Warning 
Binary_Value
37
5857_1
RD
Active on Alarm
Battery Over Temperature 
Binary_Value
38
4219_1
RD
Active on Alarm
Battery Temperature Imbalance 
Binary_Value
39
4169_1
RD
Active on Alarm
Output
Output Overload 
Binary_Value
50
5806_1
RD
Active on Alarm
Output Off Pending 
Binary_Value
51
5807_1
RD
Active on Alarm
System Output Off 
Binary_Value
52
4215_1
RD
Active on Alarm
System Shutdown - Transformer Over Temperature 
Binary_Value
53
5850_1
RD
Active on Alarm
Inverter Shutdown - Overload 
Binary_Value
54
4290_1
RD
Active on Alarm
System Shutdown - Output Short 
Binary_Value
55
5808_1
RD
Active on Alarm
System Shutdown - Low Battery 
Binary_Value
56
5809_1
RD
Active on Alarm
System Shutdown - Remote Shutdown 
Binary_Value
57
5810_1
RD
Active on Alarm
System Shutdown - Hardware Fault 
Binary_Value
58
5811_1
RD
Active on Alarm
Maximum Load Alarm 
Binary_Value
59
5851_1
RD
Active on Alarm
Inverter
Loss of Redundancy 
Binary_Value
70
5817_1
RD
Active on Alarm
Power Module Failure 
Binary_Value
71
5818_1
RD
Active on Alarm
Power Module Warning 
Binary_Value
72
5819_1
RD
Active on 
System Status
Unspecified General Event 
Binary_Value
83
5588_1
RD
Active on Alarm
Check Air Filter 
Binary_Value
84
5862_1
RD
Active on Alarm
Frame Fan Fault 
Binary_Value
85
5770_1
RD
Active on Alarm
Transformer Fan Fault 
Binary_Value
86
5863_1
RD
Active on Alarm
Transformer Overtemperature 
Binary_Value
87
5433_1
RD
Active on Alarm
No Load Warning 
Binary_Value
88
5865_1
RD
Active on Alarm