Emerson MODBUS IP Manuel D’Utilisation
BACnet Communications - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
306
Table 102 Liebert APS
™
- Binary Data
Data Label
Object Type
Instance
Object
Name
Access
Notes
Input
Rectifier Failure
Rectifier Failure
Binary_Value
1
4295_1
RD
Active on Alarm
System Input Power Problem
Binary_Value
2
4122_1
RD
Active on Alarm
System Input Current Imbalance
Binary_Value
3
4382_1
RD
Active on Alarm
Bypass
UPS Output on Bypass
UPS Output on Bypass
Binary_Value
14
4298_1
RD
Active on Alarm
Output Load on Maint. Bypass
Binary_Value
15
4299_1
RD
Active on Alarm
Bypass Not Available
Binary_Value
16
4135_1
RD
Active on Alarm
Bypass Overload
Binary_Value
17
5798_1
RD
Active on Alarm
Bypass Frequency Error
Binary_Value
18
4175_1
RD
Active on Alarm
Bypass Auto Retransfer Failed
Binary_Value
19
4138_1
RD
Active on Alarm
Battery
Battery Discharging
Battery Discharging
Binary_Value
30
4168_1
RD
Active on Alarm
Battery Manual Test In Progress
Binary_Value
31
4171_1
RD
Active on Alarm
Battery Auto Test In Progress
Binary_Value
32
4172_1
RD
Active on Alarm
Battery Test Passed
Binary_Value
33
4322_1
RD
Active on Alarm
Battery Test Failed
Binary_Value
34
4323_1
RD
Active on Alarm
Low Battery - Shutdown Imminent
Binary_Value
35
5801_1
RD
Active on Alarm
Battery Module Fault
Binary_Value
36
5856_1
RD
Active on Alarm
Battery Module Warning
Binary_Value
37
5857_1
RD
Active on Alarm
Battery Over Temperature
Binary_Value
38
4219_1
RD
Active on Alarm
Battery Temperature Imbalance
Binary_Value
39
4169_1
RD
Active on Alarm
Output
Output Overload
Output Overload
Binary_Value
50
5806_1
RD
Active on Alarm
Output Off Pending
Binary_Value
51
5807_1
RD
Active on Alarm
System Output Off
Binary_Value
52
4215_1
RD
Active on Alarm
System Shutdown - Transformer Over Temperature
Binary_Value
53
5850_1
RD
Active on Alarm
Inverter Shutdown - Overload
Binary_Value
54
4290_1
RD
Active on Alarm
System Shutdown - Output Short
Binary_Value
55
5808_1
RD
Active on Alarm
System Shutdown - Low Battery
Binary_Value
56
5809_1
RD
Active on Alarm
System Shutdown - Remote Shutdown
Binary_Value
57
5810_1
RD
Active on Alarm
System Shutdown - Hardware Fault
Binary_Value
58
5811_1
RD
Active on Alarm
Maximum Load Alarm
Binary_Value
59
5851_1
RD
Active on Alarm
Inverter
Loss of Redundancy
Loss of Redundancy
Binary_Value
70
5817_1
RD
Active on Alarm
Power Module Failure
Binary_Value
71
5818_1
RD
Active on Alarm
Power Module Warning
Binary_Value
72
5819_1
RD
Active on
System Status
Unspecified General Event
Unspecified General Event
Binary_Value
83
5588_1
RD
Active on Alarm
Check Air Filter
Binary_Value
84
5862_1
RD
Active on Alarm
Frame Fan Fault
Binary_Value
85
5770_1
RD
Active on Alarm
Transformer Fan Fault
Binary_Value
86
5863_1
RD
Active on Alarm
Transformer Overtemperature
Binary_Value
87
5433_1
RD
Active on Alarm
No Load Warning
Binary_Value
88
5865_1
RD
Active on Alarm