Emerson MODBUS IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
62
Table 21
Liebert XDP
™
- Input and Holding
Data Label
Input Holding # of Reg Scale
Notes/Units
Pumps
Pump 1 State
30385
—
1
—
0 = off
1 = on
Pump 2 State
30386
—
1
—
0 = off
1 = on
Refrigerant
Supply Refrigerant Temperature
Supply Refrigerant Temperature
30387
—
1
10
Units : deg C
Supply Refrigerant Temperature
30388
—
1
10
Units : deg F
Supply Refrig Over Temp Threshold
30411
40411
1
10
Units : deg C
Supply Refrig Over Temp Threshold
30412
40412
1
10
Units : deg F
Chilled Water
Supply Chilled Water Temperature
Supply Chilled Water Temperature
30389
—
1
10
Units : deg C
Supply Chilled Water Temperature
30390
—
1
10
Units : deg F
Supply Chilled Water Over Temp Threshold
30413
40413
1
10
Units : deg C
Supply Chilled Water Over Temp Threshold
30414
40414
1
10
Units : deg F
Chilled Water Valve Open Position
31710
—
1
—
—
System Information
System Status
30391
—
1
—
1 = Normal Operation
2 = Startup
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
System Operating State
30392
—
1
—
0 = off
1 = on
2 = standby
Auto Restart Delay
30417
40417
1
—
Units : sec
System Control Mode
30418
—
1
—
0 = Internal (Auto)
1 = External (Manual)
Maintenance Ramp
30419
—
1
—
Units : %
Calculated Next Maintenance Month
30420
—
1
—
Calculated Next Maintenance Year
30421
—
1
—
System On/Off Control
30422
40422
1
—
0 = off
1 = on
System Operating State Reason
31704
—
1
—
0 = Reason Unknown
1 = Network Display
2 = Alarm
3 = Schedule
4 = Remote System
5 = External Input
6 = Local Display
External Air
Ext Air Sensor A Temperature
Ext Air Sensor A Temperature
30393
—
1
10
Units : deg C
Ext Air Sensor A Temperature
30394
—
1
10
Units : deg F
Ext Air Sensor A Humidity
30395
—
1
10
Units : % RH
Ext Air Sensor A Dew Point Temp
30396
—
1
10
Units : deg C
Ext Air Sensor A Dew Point Temp
30397
—
1
10
Units : deg F
Ext Air Sensor B Temperature
30398
—
1
10
Units : deg C
Ext Air Sensor B Temperature
30399
—
1
10
Units : deg F
Ext Air Sensor B Humidity
30400
—
1
10
Units : % RH
Ext Air Sensor B Dew Point Temp
30401
—
1
10
Units : deg C
Ext Air Sensor B Dew Point Temp
30402
—
1
10
Units : deg F