Emerson 6 kVA Manuel D’Utilisation

Page de 16
14
Specifications
Note: Part Numbers GXT2-6000RT208 and GXT2-10000RT208 do not include internal battery kits. When calculating total unit weight, add weight of internal batteries.
LIEBERT GXT2 6 KVA 
LIEBERT GXT2 10 KVA 
Model Number 
GXT2-6000RT208
GXT2-10000RT208
Model Rating
4200W/5200VA at 127/220 (120 or 240 degrees)
8000W/8660VA at 127/220 (120 or 240 degrees)
4200W/5200VA at 120/208 (120 or 240 degrees)
8000W/8660VA at 120/208 (120 or 240 degrees)
4200W/6000VA at 120/240 (180 degrees)
8000W/10000VA at 120/240 (180 degrees)
4200W/6000VA at 115/230 (180 degrees)
8000W/10000VA at 115/230 (180 degrees)
3780W/5400VA at 110/220 (180 degrees)
7200W/9000VA at 110/220 (180 degrees)
3360W/4800VA at 100/200 (180 degrees)
6400W/8000VA at 100/200 (180 degrees)
DIMENSIONS Unit W x D x H in. (mm) 
6.9 x 24.2 x 16.9 (176 x 615 x 430)
10.5 x 26.0 x 16.9 (267 x 660 x 430)
WEIGHT lbs (kg) Unit  
67 (30.3)
109 (49.3)
INPUT AC PARAMETERS
Nominal Operating Frequency 
50 or 60 Hz (Factory Default = 60)
Factory Default VAC 
120/208 VAC at 120 degrees
L1-L2 Factory Default Input Phase Angle 
120 degrees
Allowable Input Phase Angle 
120, 180, 240 degrees, Auto-sensing on application of AC (Restrictions for L-N voltages other than 120 VAC)
Factory Default L1-N, L2-N VAC 
120 VAC nominal
Input Frequency w/o Battery Operation
40 - 70 Hz
OUTPUT AC PARAMETERS
Factory Default VAC 
120/208 VAC @ 120 degrees
L1-L2 Factory Default Output Phase Angle 
120 degrees
Allowable Output Phase Angle 
120, 180, 240 degrees Auto-sensing on initial  application of input AC
Factory Default L1-N, L2-N VAC 
120 VAC nominal
User Configurable L1-N, L2-N VAC
100/110/115/120/127 VAC, ±3%
Frequency 
50 Hz or 60 Hz, Nominal
Waveform 
Sinewave
Overload Rating
200% for 8 cycles; 130% for 10 seconds 
200% for 8 cycles then shutdown; 130% for 60 seconds 
with transfer to bypass
with transfer to bypass
ENVIRONMENTAL
Operating Temp 
+32°F to +104°F (0°C to +40°C)
Storage Temp 
+5°F to +122°F (-15°C to +50°C)
Relative Humidity 
0% to 95%, non-condensing
Operating Elevation 
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation 
50,000 ft. (15,000 m) maximum
Audible Noise 
<55 dBA, at 1 meter from  the rear; <50 dBA, at 1 meter  from  the front or sides
AGENCY
Safety 
UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI 
FCC Part 15, Subpart B, Class A
Surge Immunity 
IEEE/ANSI C62.41 Category A & B
Transportation 
ISTA Procedure 1A
INTERNAL BATTERY
Model Number 
GXT2-144BATKIT (one required)
GXT2-288RTBKIT (two required)
WEIGHT lbs (kg)
79 (35.8) (one required)
78.1 (35.5) (two required)
Type 
Valve-regulated, non-spillable, flame retardant, lead acid
Quantity x V x Rating 
12 x 12V x 9.0 AH (one required)
12 x 12V x 9.0 AH (two required)
Battery Mfg / Part # 
Yuasa / REW 45-12 FR
Recharge Time 
6 Hours to 90% capacity after full discharge into 100% load
OPTIONAL EXTENDED BATTERY CABINET
Model Number 
GXT2-144VBATT
GXT2-288RTVBATT (requires two GXT2-288RTBKIT)
DIMENSIONS W x D x H in.(mm)
3.5 x 24.2 x 16.9 (87 x 618 x 430)
7.0 x 26.0 x 16.9 (178 x 660 x 430)
WEIGHT lbs (kg) Unit
93.6 (42.5)
197.8 (89.9) (Total weight with batteries)
BATTERY PARAMETERS
Type 
Valve-regulated, non-spillable, flame retardant, lead acid
Qty x V x Rating 
12 x 12V x 9.0 AH per kit
12 x 12V x 9.0 AH per kit (two required)
Battery Mfg / Part # 
Yuasa / REW 45-12 FR
ENVIRONMENTAL
Operating Temp 
+32°F to +104°F (0°C to +40°C)
Storage Temp 
+5°F to +122°F (-15°C to +50°C)
Relative Humidity 
0% to 95%, non-condensing
Operating Elevation 
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation 
50,000 ft. (15,000m) maximum
AGENCY
Safety 
UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI 
FCC Part 15, Subpart B, Class A
Transportation 
ISTA Procedure 1A
168997_SL23172:15615 govern  7/22/08  2:30 PM  Page 15