Chapter 3. Maintenance 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
INSTALLING A FIELD EXPANSION RECTIFIER/CONVERTER 
MODULE MOUNTING SHELF SPEC. NO. 588705300 
Danger: 
Adhere to the “Important Safety Instructions” presented at the front of 
this document. 
Note:  Refer to Figure 3-4 and Figure 3-5 as this procedure is performed. 
Procedure 
1)  Remove the busbar rear shield from the existing rectifier/converter shelves.  
Remove the cut-out panel from the busbar rear shield by gently bending the 
panel until it snaps from the busbar rear shield. 
2) 
Remove the hardware from the lowest module mounting shelf’s -48V, return, and 
+24V (if present) busbars. 
3)  Install the expansion module mounting shelf directly below the bottom-most 
module mounting shelf in the rack.  Use the mounting hardware provided with the 
expansion module mounting shelf. 
Hardware build-up is: 
12-24 x 3/4" screw and flat washer, (1) set per side. 
 
 
 
 
 
 
12-24 x 3/4" screw and ground washer, (1) set per side. 
Note:  Install the ground washers so the teeth make contact with the metal on 
the mounting angles.  Torque all screws to 65 in-lbs. 
4)  Remove the busbar rear shield from the expansion module mounting shelf. 
Note:  Apply electrical anti-oxidizing compound to busbar mating surfaces before 
performing the next step. 
5)  Install the busbars provided with the expansion module mounting shelf between 
the studs on the expansion module mounting shelf and the studs on the shelf 
above it.  Secure these busbars to the expansion module mounting shelf with the 
hardware provided with the expansion module mounting shelf.  Secure these 
busbars to the shelf above the expansion module mounting shelf with the 
hardware previously removed.  Torque to 60 in-lbs. 
Hardware build-up for these connections are: 
 
M6 Nut, 
 
M6 Belleville lock washer, 
 
M6 flat washer. 
6)  Disconnect the cable coming from the distribution cabinet from the connector on 
the bottom-most existing module mounting shelf and connect this cable to the 
same connector on the expansion module mounting shelf. 
7)  Connect the open connector on the bottom-most existing module mounting shelf 
to the open connector on the expansion module mounting shelf. 
8)  Re-install the rear busbar shield previously removed from the existing module 
mounting shelf.  Re-install the rear busbar shield previously removed from the 
expansion module mounting shelf. 
9)  Refer to the Power System Installation Instructions (IM582127000) and connect 
AC input power to the expansion module mounting shelf. 
10) Refer to the Power System Installation Instructions (IM582127000) and install 
rectifier and converter modules into the expansion module mounting shelf as 
required.