Emerson 721NPBB Manuel D’Utilisation

Page de 72
UM582127000 
User Instructions 
Issue AC, January 2, 2013 
Spec. No. 582127000 (Model 721
NPBB
 
Page 28 
Chapter 4. Troubleshooting and Repair 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
Replacing a Bullet Nose Fuseholder 
Procedure 
Note:  Refer to Figure 4-2 as this procedure is performed. 
1)  Open the distribution cabinet
’s front door by turning the latch in the 
counterclockwise position. 
2)  Remove the fuse carrier from the mounted fuseholder body by pulling it straight 
out.  Hold the fuseholder body while you pull the fuse carrier from the body. 
3)  Gently rock the defective fuseholder up and down while pulling firmly outward 
until the fuseholder is free from the distribution panel. 
4)  Orient the fuseholder as shown in Figure 4-2.  Insert the terminals on the rear of 
the fuseholder into their corresponding sockets on the distribution panel.  Ensure 
the alarm contact on the back of the fuseholder makes contact with the alarm 
terminal on the spring strip.  Push fuseholder in firmly until fully seated in the 
distribution panel. 
5)  Push the fuse carrier securely back into the mounted fuseholder body.  Note that 
a polarizing key on the bottom of the carrier prevents the carrier from being 
inserted upside down. 
6)  Verify no Fuse Alarms are active. 
7)  Close the distribution cabinet
’s front door.  Turn the latch clockwise to secure the 
door.