Emerson SAG581126000 Manuel D’Utilisation

Page de 123
System Application Guide 
SAG581126000 
Spec. No. 581126000 (Model 700
NVBA
Issue AD, November 23, 2009 
 
Page 73 of 123 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
GMT-Type Load Distribution Fuses 
Features 
” (see previous section) is available for 
additional load distribution. 
Restrictions 
When used for power distribution, load should not exceed 80% of device rating, except 10 and 15 amp fuses, 
for which load should not exceed 70% of device rating. 
Ordering Notes 
1)  Order fuses as required pe
Ampere Rating 
Part Number 
Fuse Color 
18/100 (GMT-A) 
248610301 
--- 
1/4 248610200 
VIOLET 
1/2 248610300 RED 
3/4 248610500 
BROWN 
1-1/3 248610700 
WHITE 
2 248610800 
ORANGE 
3 248610900 
BLUE 
5 248611000 
GREEN 
7-1/2 248611300 
BLACK-WHITE 
10 248611200 
RED-WHITE 
15 248611500 
RED-BLUE 
Replacement 
Safety Fuse 
Cover (GMT-Y) 
102774 --- 
Replacement 
Dummy Fuse 
248872600 --- 
Table 2 
GMT Fuses