This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
AC Input Branch Circuit Protection and Wire Size Selection 
Refer to PD588705100/PD588705101/PD588705102/PD588705103/PD588705104. 
Relay Rack Frame Grounding Requirements 
Ordering Notes 
1)  For relay rack grounding requirements, refer to the current edition of the American National Standards 
Institute (ANSI) approved National Fire Protection Association's (NPFA) National Electrical Code (NEC), 
applicable local codes, and your specific site requirements. 
A customer's grounding network lead can be attached to the top of each relay rack.  Provision is made for 
installing a lead with a two-hole lug that has 1/4" bolt clearance holes on 5/8" centers.  Refer to Table 
for lug selection. 
External Alarm, Reference, and Control Wire Sizes 
Features 
♦  External alarm, reference, and control connection points are located on… 
•  J1-J4 on the optional 
 Audible Alarm and Alarm Termination Circuit Card P/N 509539, 
•  TB1 on circuit card P/N 509532, and 
•  J8 on circuit card P/N 534868 (if List 71 not installed). 
” under 
PHYSICAL SIZE INFORMATION for illustration. 
 
J1-J4 on Optional List 71 Audible Alarm and 
Alarm Termination Circuit Card P/N 509539 
Terminals 
Capacity Type 
Recm 
Wire Size 
26 to 16 
AWG 
Spring-Clamp 
22 AWG for Loop Lengths Up to 200 ft. 
18-20 AWG for Loop Lengths Over 200 ft. 
 
TB1 on Circuit Card P/N 509532 
Terminals 
Capacity Type 
Recm 
Wire Size 
26 to 16 
AWG 
Spring-Clamp 
22 AWG for Loop Lengths Up to 200 ft. 
18-20 AWG for Loop Lengths Over 200 ft. 
 
J8 on Circuit Card P/N 534868 
Terminals 
Recm Wire Size 
D-Type Connector 
22 AWG for Loop Lengths Up to 200 ft. 
18-20 AWG for Loop Lengths Over 200 ft.