1.3.7 
Power Split Feature 
The Power Split feature allows you to connect the power system controlled via the ACU+ to an existing DC 
power system instead of extending or completely replacing the existing DC power system. 
The power system controlled via the ACU+ functions as a slave system to share load (split output) with the 
existing system (master system) that requires expansion. The ACU+ does not require communication with 
the master system’s Controller. 
The Power Split feature provides for the sharing of total load in a controlled manner between the 
paralleled power systems. 
When Power Split is programmed, the ACU+ adjusts rectifier output voltage per load demands to ensure 
proper sharing between the slave and master power systems. See Figure 5. 
 
 
Figure 5 
Power Split Feature 
 
1.3.8 
Diesel Management Feature 
The Diesel Management feature is available when an SM-AC supervisory module is connected to the 
ACU+ Controller. The Diesel Management feature consists of a Diesel Test. The Diesel Test can be 
performed at specific intervals or a User can manually start the Diesel Test. The ACU+ records the test 
results.