4.8.5 
Alarm Suppressing Sub-Menu 
Here you can modify the Alarm Suppression relationships of an alarm signal. 
Alarm Suppression Explanation: If Alarm A suppresses Alarm B, when Alarm A occurs, Alarm B will not 
be reported even if the conditions of Alarm B are met. For example, AC failure alarm will suppress AC low 
voltage alarm. When AC failure occurs, the alarm conditions for both AC failure alarm and AC low voltage 
alarm are met, and both alarms should be reported. However, since the AC failure alarm suppresses the 
AC low voltage alarm, only AC failure alarm is displayed in the alarm list. 
To configure Alarm Suppression, first select the device to which the alarm signal belongs. This displays all 
the alarm signals of this device. 
Locate the alarm signal to be configured for Alarm Suppression and click on the “Modify” button for this 
alarm signal.