Chapter 2.  Operation 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
2.3 
Local Keypad and Display Access 
2.3.1 
Local Menu Navigation Keys and LCD Display 
Location and Identification: Refer to Figure 7. 
Description: There are four (4) menu navigation keys and an LCD display located on the ACU+ 
Controller’s front panel. Refer to Table 3 for the function of the menu navigation keys. 
Note:  When the LCD is lit, if no button is pushed for 8 minutes, the backlight of the LCD display 
extinguishes and the ACU+ Controller returns to the Main Screen. Press any key to re-activate the 
LCD display. 
Key Symbol 
Key Name 
Function 
ESC 
Escape 
Press this key to go back to a 
previous menu or to cancel setting 
a parameter. 
Press ESC and ENT together to 
reset the ACU+ Controller, then 
press ENT to accept or ESC to 
cancel. 
ENT 
Enter 
Press this key to go forward to the 
next menu, to select a parameter 
to edit, or to validate a parameter 
setting change. 
 
Up 
Press
 or
 to scroll through 
the menus or to change the value 
of a parameter. 
-- 
 
Down 
Press any key to silence an audible alarm. 
Table 3 
Local Menu Navigation Keys 
 
2.3.2 
Local Display Menus 
Refer to 
Note:  A valid password is required to access menus that allow changing any power system parameter. 
Navigating the Menus 
To Select a Sub-Menu: 
Press the up or down arrow keys to move the cursor up and down the list of sub-menus in the menu 
screen (selects the sub-menu), then press ENT to enter the selected sub-menu. 
To Enter a Password: 
If a password screen opens, a password must be entered to allow the User to make adjustments. To enter 
a password, with the cursor at the User Name field 
(default is “Admin”), press the down arrow key to move 
cursor down to the password line.  Press ENT
“0” is highlighted. Press the up arrow key once to change 
the “0” to”1” (default password is “1”), then press ENT twice. (Note:  If you have been assigned a unique 
User Name and password, follow this procedure to enter these.)
 
To Change a Parameter: 
Press the up or down arrow keys to move the cursor up and down the list of parameters in the menu 
screen (selects the parameter to change), then press ENT to change the selected parameter. The 
parameter field highlights. Press the up or down arrow keys to change the parameter value. Press ENT to 
confirm the change.