Emerson M820D Manuel D’Utilisation

Page de 176
UM1M820BNA 
User Instructions 
Issue AH, March 4, 2013 
Spec No. 1M820BNA (Model M820B) 
 
Spec No. 1M820DNA (Model M820D) 
 
24 
Chapter 2.  Operation 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
3)  The "Stop 
Controller" window opens. Click on the “Stop Controller” button. 
4)  A Download window opens. 
Warning:  Never navigate from this web page without first clicking on "Start Controller".  If 
you do, you will not have web access. A manual system reset is required to 
restore web access. 
5)  C
lick the “Browse….” button and navigate to the folder where the file is located. Select the file and 
then click the “Download” button. Click “Start Controller” to restart the Controller with the 
downloaded file installed. 
2.5.5 
Rebooting the Controller 
Local Menu Navigation: Press ENT and ESC at the same time to reset the ACU+ Controller. 
WEB Menu Navigation: Maintenance / Restore Factory Defaults / 
select “Reboot Controller”. 
2.5.6 
Changing the Local LCD Display Contrast 
Local Menu Navigation: Press ENT and UP ARROW or ENT and DOWN ARROW while in the Main 
Screen to change the contrast of the LCD display. 
WEB Menu Navigation: none. 
2.5.7 
Disabling the Local Keypad Sound 
Local Menu Navigation: Main Menu / Settings / Controller / Keypad Voice. 
To disable the keypad sound, set "Keypad Voice" to "Off". 
WEB Menu Navigation: none. 
2.5.8 
Changing the Date 
Local Menu Navigation: Main Menu / Settings / Controller / Date. 
After selecting Date (by pressing ENT when the cursor is in the Date field), use  and  to select the year 
then press ENT, next use  and  to select the month then press ENT, and finally use  and  to select 
the day then press ENT
WEB Menu Navigation: Maintenance / Time Sync. 
2.5.9 
Changing the Time 
Local Menu Navigation: Main Menu / Settings / Controller / Time. 
After selecting Time (by pressing ENT when the cursor is in the Time field), use  and  to select the 
hour then press ENT, next use  and  to select the minute then press ENT, and finally use  and  to 
select the second then press ENT
WEB Menu Navigation: Maintenance / Time Sync. 
2.5.10  Adding, Deleting, and Modifying Users 
Local Menu Navigation: none. 
WEB Menu Navigation: Refer to 
2.5.11  Assigning Severity Level to Alarms 
Local Menu Navigation: Main Menu / Settings / Alarm Setting / Alm Severity. 
WEB Menu Navigation: Configuration / Signal Information Modification / select entry 
from “Query Device 
Type” list / select “Alarm Signal” from “Signal Type” list / select entry from “New Level” list / press “Set”.