Chapter 3. Maintenance 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
CHANGING THE ACU+ LVD CONTROL 
LEVEL FOR A CONTACTOR 
The ACU+ Controller has two available LVD control levels (LVD1 and LVD2).  The level 
used to control a contactor is determined by which connector on the LVD circuit card its 
control leads are plugged into.  To change the LVD control level for a contactor, simply 
switch which LVD connector it is plugged into (if an open connector is available) on the 
LVD circuit card.  Refer to Figure 4-13 and Figure 4-14 for connector location and 
function. 
Note:  DO NOT change a Low Voltage Load Disconnect contactor to LVD Control Level 
2 (LVD2) if the system is furnished with a Low Voltage Battery Disconnect 
contactor.