Emerson 710NPBA Manuel D’Utilisation

Page de 60
UM581127000 
User Instructions 
Issue AB, March 22, 2012 
Spec. No. 581127000 (Model 710
NPBA
 
Page 30 
Chapter 4. Troubleshooting and Repair 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
Circuit Card Replacement Procedures 
Warning:  Circuit cards used in this power system contain static-sensitive devices.  
Read the Static Warning at the front of this document before performing 
any of the following procedures. 
General 
The following circuit card replacement procedures can be performed with the system 
operating. 
Refer to Figure 2-1 for circuit card locations. 
Caution:  When performing any step in these procedures that requires removal or 
installation of hardware, use caution to ensure no hardware is dropped 
and left inside the cabinet; otherwise service interruption or equipment 
damage may occur. 
Note:  When performing any step in these procedures that requires removal of existing 
hardware, retain all hardware for use in subsequent steps. 
System Interface Circuit Card Replacement 
Procedure 
1)  Performing this procedure may activate external alarms.  Do one of the following.  
If possible, disable these alarms.  If these alarms cannot be easily disabled, 
notify the appropriate personnel to disregard any future alarms associated with 
this system while the procedure is being performed. 
Danger:  Performing the next steps exposes service personnel to battery 
potential.  Exercise extreme caution not to inadvertently contact or 
have any tool inadvertently contact any energized electrical 
termination. 
2)  Open the distribution cabinet
’s front door by turning the latch in the 
counterclockwise position. 
Warning:  Damage to the circuit card may result if the next step is not followed. 
3)  Connect an approved grounding strap to your wrist.  Attach the other end to a 
suitable ground. 
4)  Remove the top and front panels to access the circuit cards at the bottom of the 
distribution cabinet. 
5)  Carefully label any wires connected to the customer connection terminal block on 
the circuit card.  These wires must be connected to the same terminals on the 
replacement circuit card.  Refer to Figure 4-9. 
6)  Carefully label the connectors plugged into the circuit card.  These connectors 
must be plugged into the same connectors on the replacement circuit card.  
Refer to Figure 4-9. 
Danger:  In the next step, external wiring may be energized from an external 
source.  DO NOT allow bare wire ends to contact any grounded or 
energized object. 
7)  Remove the external wiring from the customer connection terminal block.  DO 
NOT allow the bare wire end to contact any grounded or energized object.  
Isolate the wire end with electrical tape.  Repeat for each wire to be removed. 
8)  Unplug all connectors plugged into the circuit card.