Operator Control and Display Panel
89
Settings
Display contrast
Adjust the LCD display contrast
Date format set
Choose the format for date display: YYYY MM DD, DD MM YYYY and MM DD 
YYYY
Date & time
Set the date and time
Comm1 baud rate
Communication baud rate setting for Liebert IntelliSlot 1
Comm2 baud rate
Communication baud rate setting for Liebert IntelliSlot 2
Comm3 baud rate
Communication baud rate setting for Liebert IntelliSlot 3
Communication address
This setting is applicable to RS485 communication mode
Communication mode
Communication Mode Setting
Callback times
When Liebert IntelliSlot 1 Communication mode is Modem, this parameter sets 
the number of times a number is redialed to send an alarm notification.
Phone No.1
When Liebert IntelliSlot 1 Communication mode is Modem, this is the first 
phone number to be dialed (to send an alarm notification).
Phone No.2
When Liebert IntelliSlot 1 Communication mode is Modem, this is the second 
phone number to be dialed (to send an alarm notification).
Phone No.3
When Liebert IntelliSlot 1 Communication mode is Modem, this is the third 
phone number to be dialed (to send an alarm notification).
Command password
User can modify the command password.
Protocol
System protocol
Command
(start / stop 
battery & 
system 
tests)
Battery maintenance test
This test performs a partial discharge of the battery to obtain a rough estimate 
of the battery capacity. Load must be between 20% and 80%.
Battery capacity test
This test performs a full discharge of the battery to obtain a precise measure of 
the battery capacity. Load must be between 20% and 80%.
System test
This is a self-test of the UPS. When the user activates this function, a pop-up 
window appears about 5 seconds later to show the results.
Stop testing
Manually stops a battery maintenance test, battery capacity test or system 
test.
Freshening Charge
Allows a temporary Equalize charge for the batteries. This charge is 
configurable for 1 to 36 hours.
Stop Freshening Charge
Manually stops a Freshening Charge.
Modem Auto-answer 
enabled
Manually enable the modem's auto-answer function.
Run Time
UPS Run Time
UPS Run Time
Byp Run Time
Bypass Run Time
Version
UPS model
Provides UPS model information—for example, 208V-60Hz.
Monitor Version
Monitor Firmware Version
Rectifier Version
Rectifier Firmware Version
Inverter Version
Inverter Firmware Version
Bypass Version
Bypass Firmware Version
Table 27
UPS menus and data window items (continued)
Menu Type
Item Type
Explanation