Operation
15
Liebert
®
NX
2.4.1 Load on Bypass
In this operating mode, the connected loads are supplied from line power via the Static Bypass 
Switch. The Static Bypass Switch is used to provide power to the loads. If an overload or short-circuit 
on UPS output occurs, the Static Bypass Switch is automatically activated to provide uninterrupted 
power to the loads. The Bypass operating condition is displayed. From this operating mode, the UPS 
automatically reverts to on-line operation after the fault is corrected. Bypass operation can also be 
specifically selected from the control panel using the push button.
Load on Bypass is shown in Figure 13The UPS system could be in this mode of operation during 
either initial startup or UPS system shutdown or isolation for maintenance.
NOTICE
Risk of unexpected power loss. Can cause equipment damage.
When the critical load is being supplied power from the bypass line, the load is vulnerable to 
utility failure and fluctuations.
Figure 13 Load on bypass
Figure 14 Load on bypass, UPS available
Figure 15 Load on UPS, bypass available
DC 
Bus
BFB
UPS Module
To DC Supply
Module Rectifier
AC Input
Module Bypass 
AC Input
UPS Output
Critical 
Load
DC 
Bus
BFB
UPS Module
To DC Supply
Module Rectifier
AC Input
Module Bypass 
AC Input
UPS Output
Critical 
Load
BFB
UPS Module
To DC Supply
Module Rectifier
AC Input
Module Bypass 
AC Input
UPS Output
Critical 
Load
DC 
Bus