Specifications and Technical Data
107
Table 44
UPS currents and terminals—Output 208V
Unit
Rating
Nominal
Output
Current
OCP Device
Rating
Bolt Size
75°C Wire
Current, tot
Wire
Maximum Recommended Lug (T&B)
Compression
Lug Two Hole
3/8" Bolt
Mechanical
Lug Two Hole
3/8" Bolt
15
42
70
M10 (3/8")
130
(1) #1
54857BE
32209
30
83
150
M10 (3/8")
150
(1) 1/0
54860BE
32209
45
125
200
M10 (3/8")
175
(1) 2/0
54862BE
32209
60
167
300
M10 (3/8")
230
(1) 4/0
54866BE
32211
75
208
350
M10 (3/8")
300
(2) 1/0
54860BE
32209
90
250
400
M10 (3/8")
350
(2) 2/0
54862BE
32209
Table 45
UPS currents and terminals—Battery (288V string)
Unit
Rating
Battery
Current
OCP Device
Rating
Bolt Size
75°C Wire
Current, tot
Wire
Maximum Recommended Lug (T&B)
Compression
Lug Two Hole
3/8" Bolt
Mechanical
Lug Two Hole
3/8" Bolt
15
67
80
M10 (3/8")
130
(1) #1
54857BE
32209
30
135
150
M10 (3/8")
175
(1) 2/0
54862BE
32209
45
202
225
M10 (3/8")
230
(1) 4/0
54866BE
32211
60
269
300
M10 (3/8")
300
(2) 1/0
54860BE
32209
75
336
350
M10 (3/8")
400
(2) 3/0
54864BE
32211
90
404
450
M10 (3/8")
460
(2) 4/0
54866BE
32211
Table 46
AC/AC efficiency, loss and air exchange
AC/AC Efficiency
Data
Normal mode (dual conversion), %
94 maximum
Inverter Efficiency (DC/AC) (battery at nominal voltage 288VDC and full-rated linear load)
Rated Power, kVA
15-90
Battery Mode, %
94
Heat Losses & Air Exchange
Rated Power, kVA
15
30
45
60
75
90
Normal Mode, kW
0.9
1.8
2.7
3.6
4.5
5.4
No Load, kW
0.3
0.6
0.9
1.2
1.5
1.8
Maximum forced air cooling
(front intake, rear exhaust), L/sec (m
3
/hr)
102 (173)
204 (346)
306 (519)
408 (692)
510 (865)
612 (1038)
Heat Dissipation, BTU/Hr (kWH)
Without Transformer
3074 (0.9)
6147 (1.8)
9220 (2.7)
12295 (3.6)
15368 (4.5)
18442 (5.4)
With Transformer, 480V
13928 (4)
17001 (5)
20074 
(5.9)
23149 (6.8)
26222 (7.8)
29296 (8.6)
With Transformer, 600V
13726 (4)
16772 
(4.9)
19845 
(5.8)
22920 (6.7)
25993 (7.6)
29067 (8.5)
Top Fan Maximum Forced Air Cooling:  467 L/sec (1680 m
3
/hr) total for 2 fans