Emerson 115-208 Manuel D’Utilisation

Page de 132
2
Ground Leakage Currents
  
NOTICE
Risk of improper ground connection. Can cause equipment damage.
Ground connection is essential before connecting the input supply. This equipment must be 
grounded in accordance with local electrical codes. Maximum load must not exceed that 
shown on the UPS rating label.
NOTICE
Risk of improper improper electromagnetic shielding. Can cause radio communication 
interference.
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J 
of the FCC rules. These limits provide reasonable protection against harmful interference in a 
commercial environment. This unit generates, uses and radiates radio frequency energy and, 
if not installed and used in accordance with this instruction manual, may cause harmful 
interference to radio communications. This unit is not designed for use in a residential area. 
Operation of this unit in a residential area may cause harmful interference that the user is 
solely responsible for correcting.
!
CAUTION
Risk of electric shock from high leakage current. Can cause injury, property damage and 
death.
EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY.
Earth leakage current exceeds 3.5 mA and is less than 1000 mA.
Transient and steady-state earth leakage currents, which may occur when starting the 
equipment, should be taken into account when selecting instantaneous RCCB or RCD devices.
Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional 
pulses (Class A) and insensitive to transient current pulses.
Note also that the earth leakage currents of the load will be carried by this RCCB or RCD.
This equipment must be earthed in accordance with the local electrical code of practice.
!
WARNING
Risk of electric shock. Can cause injury, property damage and death.
Under typical operation and with all UPS doors closed, only normal safety precautions are 
necessary. The area around the UPS system should be kept free of puddles of water, excess 
moisture and debris.
Special safety precautions are required for procedures involving handling, installation and 
maintenance of the UPS system and the internal batteries (internal batteries accommodated 
by 45kVA frame only). Observe all safety precautions in this manual before handling or 
installing the UPS system as well as during all maintenance procedures. Observe all battery 
safety precautions before working on or near the battery.
This equipment contains several circuits that are energized with high voltage. Only 
test equipment designed for troubleshooting should be used. This is particularly true for 
oscilloscopes. Always check with AC and DC voltmeters to ensure safety before making 
contact or using tools. Even when the power is turned Off, dangerously high electric charges 
may exist within the UPS.
All power and control wiring should be installed by a qualified electrician. All power 
and control wiring must comply with the NEC and applicable local codes.
ONLY qualified service personnel should perform maintenance on the UPS system. 
When performing maintenance with any part of the equipment under power, service 
personnel and test equipment should be standing on rubber mats. The service personnel 
should wear insulating shoes for isolation from direct contact with the floor (earth ground).
Never work alone, even if all power is removed from the equipment. A second person should 
be standing by to assist and summon help in case an accident should occur.