Emerson 000-VA Manuel D’Utilisation

Page de 48
Controls and Indicators
21
Liebert
®
 GXT3
off power to the output sockets and connected loads. Perform all necessary shutdown 
procedures on connected loads before pressing this button twice.
7.3
Load Level Indicators (4 Green, 1 Amber)
The load level indicator is composed of five sets of LED bars that illuminate to indicate the relative 
load on the UPS output in 25% increments (±5%). The load level indicator will illuminate as shown in 
Figure 13.
The load level indicators display the approximate electrical load placed upon the UPS at all times.
Figure 13 Load level indicators.
7.4
Battery Level Indicators (5 Green)
The battery level indicator is composed of five sets of LED bars that illuminate and flash to indicate 
the battery capacity level. The Liebert GXT3 battery capacity level is shown in 20% increments (±5%). 
The battery level indicators will illuminate as shown in Figure 14
The battery level indicators display approximate battery capacity at all times. 
The Liebert GXT3 is equipped with automatic and remote battery test features. The default setting is 
for the automatic test to occur every 14 days (this option is user-configurable) if mains has not been 
interrupted. Should the battery fail this test, the red Fault indicator LED along with the A and C 
diagnostic LEDs will illuminate and an alarm will sound (refer to 11.0 - Troubleshooting). The 
remote test feature functions with Liebert MultiLink
®
 and can remotely initiate the battery test.
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
0 - 25%
Overload
76 - 100%
51 - 75%
26 - 50%