Chapter 3  Electrical Installation      15 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
Chapter 3   Electrical Installation 
This chapter introduces the electrical installation of the HIPULSE U UPS, including the procedures or methods for 
power cabling and control cabling, and the distance from floor to connection point. 
The UPS requires both power cabling and control cabling once it has been mechanically installed. All control cables, 
whether screened or not, should be run separate from the power cables in metal conduits or metal ducts which are 
electrically bonded to the metalwork of the cabinets to which they are connected. 
3.1   Power Cabling 
Warning 
BEFORE CABLING UP THE UPS, ENSURE THAT YOU ARE AWARE OF THE LOCATION AND OPERATION OF THE 
EXTERNAL ISOLATORS THAT CONNECT THE UPS INPUT/BYPASS SUPPLY TO THE MAINS DISTRIBUTION PANEL.   
CHECK THAT THESE SUPPLIES ARE ELECTRICALLY ISOLATED, AND POST ANY NECESSARY Warning SIGNS TO 
PREVENT THEIR INADVERTENT OPERATION. 
 
For cable entry, refer to 2.3.5  Cable Entry
3.1.1   System Configuration 
The power cables of the system must be size with respect to the following description: 
Module input cables 
The input cables must be sized for the maximum input current, including the maximum battery recharge current, 
given in the Table 3-1, with respect to the module rating and the input AC voltage. 
Module bypass and output cables 
The bypass and output cables must be sized for the nominal output current, given in the Table 3-1, with respect to the 
module rating and the output AC voltage. 
Battery cables 
Each UPS module has its own battery which is connected using two cables, one positive and one negative. The 
battery cables must be sized for the battery discharge current at the end-of-discharge voltage, as given in Table 3-1 
with respect to the module rating. 
3.1.2   Cable Rating 
The power cables can be sized to suit the UPS module rating according to Table 3-1. 
Table 3-1    UPS module power cable rating 
Nominal current: Amps 
Busbar stud size 
Input mains with full battery recharge
(subtract 5% for 12-pulse) 
Bypass/output at full load 
Input/output 
cables 
UPS rating 
(kVA) 
380V 
400V 
415V 
380V 
400V 
415V 
Battery at 
minimum battery 
voltage (400Vac)* 
Bolt 
Ø 
Battery 
cables 
Torque 
(Nm) 
160 341 324  312  243 
231 
222 
464  M10 
11 
M10 
bolt
26 
200 426 405  390  304 
289 
278 
580  M10 
11 
M10 
bolt
26 
300 634 602  572  456 
434 
413 
870  M12 
13 
M12 
bolt
50 
400 848 803  772  607 
578 
556 
1160  M12 
13 
M12 
bolt
50 
Note*: Maximum battery discharge current at 380Vac supply increases by 3%, and for a 415Vac supply decreases by 3%