Chapter 4  Operator Control And Display Panel      31 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
No. 
Menu 
Item 
Explanation 
Communication address 
This setting applies to RS485 communication and the 
“one-to-multiple points” communication mode of parallel system. It is 
required to set the parameter Host communication mode of COM1 in 
parallel system to Multipoint to point using background software 
before setting the communication address of each UPS module 
Communication mode 
Reserved modem function. No need to change the default setting 
“RS232” 
Callback times 
(reserved) 
Phone No.1 
(reserved) 
Phone No.2 
(reserved) 
Phone No.3 
(reserved) 
9 Settings 
Command password 
Modifies password for the Command menu. 
Use the Shift key (F1) to highligt Command Password, press the 
Enter key (F4).   
Enter each old password digit with up arrow (F2) and use right arrow 
(F3) to access next field. Press the Enter key (F4) when all digits 
have been entered. 
Follow prompts and repeat the process for new password   
Battery maintenance test 
Manually initiates battery maintenance test, which will lead to the 
battery being partly discharged, for rough assessment of the battery 
capacity. 
The Load must exceed 20% and be less than 80% of rated UPS 
capacity, and the battery must have been float charging for 5 hours or 
more. 
Use the Shift key (F1) and up and down arrow keys (F2, F3) to 
highligt the desired test. Press the Enter key (F4).   
Enter each password digit with up arrow (F2) and use right arrow (F3) 
to access next field. Press the Enter key (F4) when all digits have 
been entered 
Battery capacity test 
Manually initiates battery capacity test, which will lead to the battery 
being completely discharged, for accurate assessment of the battery 
capacity. 
The Load must exceed 20% and be less than 80% of rated UPS 
capacity, and the battery must have been float charging for 5 hours or 
more. 
Use the Shift key (F1) and up and down arrow keys (F2, F3) to 
highligt the desired test. Press the Enter key (F4).   
Enter each password digit with up arrow (F2) and use right arrow (F3) 
to access next field. Press the Enter key (F4) when all digits have 
been entered 
System test 
Manually initiates the system test. 
The user actives this function, after 5 seconds, a pop window will 
appear to show the result of this diagnosis: Rectifier, Inverter, Monitor 
OK or Fault 
Stop testing 
Manually stop the test, including maintenance test, capacity test and 
system test 
Freshening charge 
Manually initiates freshening charge, when the battery is not in boost 
charge state.   
Use the Shift key (F1) and up and down arrow keys (F2, F3) to 
highlight this item. Press the Enter key (F4). 
Enter each password digit with up arrow (F2) and use right arrow (F3) 
to access next field. Press the Enter key (F4) when all digits have 
been entered 
10 Command
*
 
Stop freshening charge 
Manually stop the freshening charge 
Monitor Version:Vxxx 
Rectifier Version:Vxxx 
Inverter Version:Vxxx 
Displays UPS firmware versions, including inverter, rectifier, 
monitoring board firmware versions 
11 Version 
UPS model 
Displays UPS model information; for example, 380V-50Hz 
Note*: password controlled. The default passward is “12345”, please enter Settings=>Command password to change the 
password. In case the password is lost, please contact the local customer service center of Emerson