Emerson 160 Manuel D’Utilisation

Page de 79
58      Chapter 8  Specifications 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
Chapter 8   Specifications 
This chapter provides the specifications of the HIPULSE U UPS. 
8.1   Conformity And Standard   
Table 8-1    Conformity and standard 
Description 
Year 
Normative references 
Safety requirements 
1999 
IEC60950-1, IEC62040-1-1, UL1778 
EMC 2005  IEC/EN62040-2 
Design and test methods 
1999 
IEC62040-3 
 
8.2   Environmental Requirements 
Table 8-2    Environmental requirements 
Power rating (kVA) 
Item 
Unit 
160 
200 
300 
400 
Operating Temperature 
°C 
0~40 
Maximal temperature for 8hr day 
°C 
40°C (derate power by 1.5% per °C between 40°C and 50°C 
Mean Temperature for 24hr 
°C 
Maximally 35 
Relative humidity 
≤95% at 20°C 
Altitude of operation 
≤1000m asl (derate power by 1% per 100m between 1000m and 2000m) 
Storage temperature and transport 
temperature 
°C 
-25 to 70 
 
8.3   Mechanical Characteristics 
Table 8-3    Mechanical characteristics 
Power rating (kVA) 
Item 
Unit 
160 
(6-pulse) 
160 
(12-pulse) 
200 
(6-pulse) 
200 
(12-pulse) 
300 
(6-pulse) 
300 
(12-pulse) 
400 
(6-pulse) 
400 
(12-pulse) 
Height mm 
1900 
Width 
mm 
1250 1640 1250 1640 1640 2280 2280 2280 
Depth mm 
875 
Weight 
kg 
1200 1725 1350 2000 1600 2200 2100 2750 
Ventilation 
By internal intake fans 
Airflow m
3
/h 
2590 2750 2750 2910 5350 5350 6150 6150 
Cable entry 
Bottom or either side (top optional) 
 
8.4   Electrical Characteristics (Input Rectifier) 
Table 8-4  Electrical characteristics (input rectifier) 
Power rating (kVA) 
Item 
Unit 
160 
(6-pulse) 
160 
(12-pulse) 
200 
(6-pulse) 
200 
(12-pulse) 
300 
(6-pulse) 
300 
(12-pulse) 
400 
(6-pulse) 
400 
(12-pulse) 
Rated mains voltage 
Vac  380, 400, or 415 
Supply 
Three phase without neutral 
Input voltage 
tolerance
 1
 
%  ±15, (maxmally, from 290Vac to 498Vac) 
Frequency Hz 
50 or 60 
Input frequency 
tolerance 
Hz 45~65