Emerson 240V Manuel D’Utilisation

Page de 44
Introduction
5
1.2
Modes of Operation
Normal Mode
The Power Module rectifiers derive power from a utility AC source and supply regulated DC power to 
the inverter. The module’s inverter regenerates precise AC power to supply the connected equipment. 
The battery charger is in the Power Module and maintains a float-charge on the batteries.
Backup Mode
When AC utility fails, the connected equipment is supplied power by the inverter, which obtains 
energy from the Battery Modules. The output power equipment will not be interrupted during the 
failure or restoration of the AC utility source.
Auto Restart Mode
After a power outage and complete battery discharge, and once AC utility is restored, the UPS will 
automatically restart and resume supplying power to connected equipment. This feature is enabled at 
the factory, but can be disabled by the user. The user can also program two auto restart delay settings:
1. Battery capacity level (%)
2. Countdown timer
Bypass Mode
The bypass provides an alternate path for power to the connected equipment and operates in the fol-
lowing manner:
• Automatic
In the event of an internal fault or should the inverter overload capacity be exceeded, the UPS 
performs an automatic transfer of the connected equipment from the inverter to the bypass 
source.
• Manual
Should the UPS need to be taken out of service for limited maintenance or repair, manual activa-
tion of the bypass will cause an immediate transfer of the equipment from the inverter to the 
bypass source.