Emerson 10-30kVA Manuel D’Utilisation

Page de 80
Installation
4
1.0
I
NSTALLATION
The Liebert NX™ UPS is designed primarily for telecommunications and data processing applica-
tions. Liebert Corporation neither recommends nor knowingly sells this product for use with life sup-
port and other designated “critical” devices.
This section describes the NX’s environmental requirements and mechanical considerations that 
must be taken into account when planning the positioning and cabling of the UPS equipment.
Because every site is unique, this section presents a guide to general procedures and practices that 
should be observed by the installing engineer, rather than step-by-step installation instructions.
1.1
External Inspections
1. While the UPS system is still on the truck, inspect the equipment and shipping container(s) for 
any signs of damage or mishandling. Do not attempt to install the system if damage is apparent. 
If any damage is noted, file a damage claim with the shipping agency within 24 hours and contact 
Liebert Global Services at 1-800-LIEBERT to inform them of the damage claim and the condition 
of the equipment.
2. Compare the contents of the shipment with the bill of lading. Report any missing items to the 
carrier and your local Liebert representative immediately.
1.2
Internal Inspections
1. Remove any packaging material, then visually examine the UPS and battery equipment for 
transit damage, both internally and externally. Report any such damage to the shipper and to 
Liebert immediately.
2. Check the nameplate inside the cabinet door to verify that the model number and rating 
correspond to the ones specified. Record the model number and serial number in the front of this 
installation manual. This information is necessary should service be required.
3. Check for loose connections or unsecured components in the cabinet.
4. Check for shipping damage to internal components.
!
WARNING
Do not apply electrical power to the UPS equipment before the arrival of the commissioning 
engineer.
!
WARNING
The UPS equipment should be installed by a qualified engineer in accordance with the 
information contained in this section.
!
WARNING
Special care should be taken when working with the batteries associated with this equipment. 
When connected together, the nominal battery voltage is 288VDC and is potentially lethal.
• Eye protection should be worn to prevent injury from accidental electrical arcs.
• Remove rings, watches and all metal objects.
• Only use tools with insulated handles.
• Wear rubber gloves.
If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in 
a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with skin, the affected area should be washed immediately 
with large amounts of water.
NOTE
The NX UPS can be used in TN utility system.