Emerson 10-30kVA Manuel D’Utilisation

Page de 80
Electrical Connections
18
Firmware M200 or Later
The UPS has an Emergency Power Off (EPO) function operated by a button on the control panel or by 
a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.
The X2 slot, shown in Figure 11, is the remote EPO input interface. The EPO has a NO/NC contact 
point becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1.
If an external Emergency Stop facility is required, it is connected terminals X2: 1&2 or X2: 3 and 4 of 
the auxiliary terminal block (X2). It also is connected to the Normally Open or Normally Closed 
remote stop switch between these two terminals using shielded cable (see Figure 11 and Table 6). I
this function is not used, terminals X2: 3 and 4 must be opened and X2: 1 and 2 must be closed.
Figure 11 EPO wiring for firmware M200 or later
Table 6
EPO input contact relays
Position
Name
Description
J28.1
EPO_NC
EPO Activated when opened to J28.2
J28.2
EPO_NC
EPO Activated when opened to J28.1
J28.3
EPO_NO
EPO Activated when shorted to J28.4
J28.4
EPO_NO
EPO Activated when shorted to J28.3
NOTE
The Emergency Stop action within the UPS shuts down the rectifier, inverter and static 
bypass. It does not internally disconnect the input power supply. To disconnect ALL power to 
the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.
NOTE
Normally Closed EPO – X2: 1,2, these terminals are supplied factory-linked on the monitor 
board and must remain installed if using NC contacts.
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded 
for maximum runs between 82 and 164 feet (25-50m), respectively.
EPO - NO
EPO - NC
J28
X2