Emerson 10-30kVA Manuel D’Utilisation

Page de 80
Battery Installation
22
3.4.3 Installation Considerations
Position—Liebert battery cabinets come in versions specific to either the left or right side of the 
UPS. Control wires and power cables are cut to different lengths for the different versions. If the sys-
tem includes a matching maintenance bypass cabinet (MBC), the MBC should be mounted to the left 
of the UPS (nearest the busbars) and the battery cabinet(s) should be installed to the right of the 
UPS. Otherwise, left-side placement of the battery cabinet is preferable.
The battery cabinet(s) are designed to be located conveniently next to each UPS module, and are also 
available in stand-alone configurations with painted side panels. The front access design eliminates 
side and rear service clearance requirements. Refer to Table 33 for battery cabinet dimensions and 
weights.
Bolt-On Cabinets—Matching battery cabinets are designed to bolt onto the side of the UPS module 
cabinet. Use bolts that ship with each unit to connect cabinet frames at posts, two places in the front 
and two places in the rear.
Service Clearance—Allow front access to the battery cabinet at all times for maintenance and ser-
vicing. Electrical codes require that the battery cabinet be installed with no less than 3 feet (1m) of 
clearance at the front of the cabinet when operating. Side and rear panels do not require service clear-
ance.
Cables—Cables may be run between the cabinets through cutouts in the top of the cabinet, eliminat-
ing the need for external conduit runs. Route cables before moving cabinets into final position for bolt-
ing together. No top or bottom entry cables are required, except for remotely located cabinets which 
require conduits. Refer to Figure 15.
Software—To allow the UPS to accurately display the battery run time, the number of battery cabi-
nets must be noted when performing initial startup and setup using the configuration software. This 
is to be performed by the Liebert Global Services customer engineer when commissioning the unit.
Casters and Adjustable Stops—The adjustable stops are not designed to bear the full weight of the 
cabinet. Lower the stops until they are finger-tight in contact with the floor. Then tighten a small 
amount with a wrench (less than two turns) to give a good friction fit. When mounting the battery 
cabinet on seismic stands, ensure that the casters are bearing the weight of the cabinet.
Battery Support Tray—Be sure to connect the battery tray support to the front of the cabinet 
before sliding a battery tray out for connection or service. Without the support, the battery tray may 
fall out of the cabinet. See Figure 16 for details.