Emerson 10-30kVA Manuel D’Utilisation

Page de 80
UPS Specifications
39
6.4
UPS Electrical Characteristics
Table 10
UPS terminal
Input (for single-input unit)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP
Device
Rating
Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10
28
35
42
45
6M (1/4”)
54105
62204
15
42
53
63
70
6M (1/4”)
54106
62204
20
56
70
84
90
6M (1/4”)
54107
62204
30
83
104
125
125
6M (1/4”)
54152
62205
Rectifier input (for dual input unit only)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP
Device
Rating
Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10
25
31
37
40
6M (1/4”)
54130
62204
15
37
47
57
60
6M (1/4”)
54106
62204
20
50
63
76
80
6M (1/4”)
54107
62204
30
75
94
113
125
6M (1/4”)
54152
62205
Bypass input (for dual input units)
Unit
Rating 
Nominal 
Input
Current
OCP
Current 
OCP
Device
Rating
Bolt Size 
Maximum Recommended Lug
Lug T&B
One Hole 
54000 
Lug T&B
One Hole 
REDDY 
10 28  35  35 
6M 
(1/4”) 
54105  62204 
15 42  53  60 
6M 
(1/4”) 
54106  62204 
20 56  70  70 
6M 
(1/4”) 
54107  62204 
30 83
104  110 
6M 
(1/4”) 
54152  62205 
Output
Unit
Rating
Nominal
Output
Current
OCP
Current
OCP
Device
Rating
Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10
28
35
35
6M (1/4”)
54130
62204
15
42
53
60
6M (1/4”)
54106
62204
20
56
70
70
6M (1/4”)
54106
62204
30
84
105
110
6M (1/4”)
54108
62205
Battery
Unit
Rating
Battery
Current
OCP
Current
OCP
Device
Rating
Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10/15
55
55
70
6M (1/4”)
54106
62204
20/30
110
110
125
8M (5/16”)
54153
62212