Emerson 10-30kVA Manuel D’Utilisation

Page de 80
Specifications and Technical Data
61
15
D, M
240
47
60
208
42
60
15
E, N
480
24
30
480
18
30
15
E, N
600
19
30
600
14
20
15
E, N
220
53
70
220
39
50
10
A, J
208
35
50
208
28
40
10
B, K
480
16
20
208
28
40
10
B, K
600
12
15
208
28
40
10
B, K
220
34
50
208
28
40
10
C, L
480
16
20
480
12
15
10
C, L
600
13
20
600
10
15
10
C, L
220
35
50
220
26
40
10
D, M
480
16
20
208
28
40
10
D, M
600
13
15
208
28
40
10
D, M
208
36
50
208
28
40
10
D, M
220
34
50
208
28
40
10
D, M
240
32
40
208
28
40
10
E, N
480
16
20
480
12
15
10
E, N
600
13
20
600
10
15
10
E, N
220
35
50
220
26
40
Table 30
Maintenance bypass cabinet electrical data (dual input)
kVA Type
System
I/P Voltage
(VAC)
Rectifier
Max Input
Current
Rectifier
Input OCP
CB Size (A)
Bypass 
Max Input
Current
Bypass
Input OCP
CB Size (A)
O/P Voltage
(VAC)
Nominal O/P
Current Rating (A)
Output OCP
CB Size (A)
30
F, P
480
42
50
47
50
208
83
125
30
F, P
600
33
40
37
40
208
83
125
30
F, P
208
95
125
107
125
208
83
125
30
F, P
220
90
125
101
125
208
83
125
30
F, P
240
83
100
93
100
208
83
125
20
F, P
480
28
40
31
40
208
55
70
20
F, P
600
22
30
25
30
208
56
70
20
F, P
208
64
80
71.5
80
208
56
70
20
F, P
220
61
80
68
70
208
56
70
20
F, P
240
56
70
62
70
208
56
70
Table 29
Maintenance bypass cabinet electrical data (single input) (continued)
kVA Type
Maintenance
Bypass
I/P Voltage
(VAC)
Bypass Cabinet
Max Input
Current
Cabinet
Input OCP
CB Size (A)
O/P Voltage
(VAC)
Nominal O/P
Current Rating (A)
Output
OCP CB Size (A)