Emerson 10-30kVA Manuel D’Utilisation

Page de 80
Installation Drawings
50
Figure 37 Lineup detail—SlimLine distribution cabinet to NX
Table 19
Liebert-supplied interconnect wiring—SlimLine distribution cabinet to NX
Run
From
To
Conductors
A
Distribution Cabinet
Load AC Connection
Isolated Ground
B
Distribution Cabinet 
Load AC Connection
Neutral
Distribution Cabinet
C
Distribution Cabinet 
Load AC Connection
Ground
Distribution Cabinet
D
Distribution Cabinet 
Load AC Connection
PH A,B,C
E
UPS Module AC Output
Distribution Cabinet 
PH A, B, C
G
UPS Module AC Output
Distribution Cabinet
Neutral
H
UPS Module AC Output
All Ground Connections
Ground
E
E
H
G
B
D
G
H
A
C
D
H
NOTES:
1. All Liebert-supplied cable will need to be repositioned prior to and while setting the cabinets in their 
installed location.
2. All interconnection cables and hardware supplied by Liebert.
3. AC connections must be made to the UPS module before attaching.
4. See Figure 45 for placement of distribution cabinet.
5. Refer to the individual drawing of each piece of equipment for additional details.