Electrical Connections
20
3.3
Dry Contacts
The UPS provides input dry contacts and output dry contacts.
3.3.1 Input Dry Contacts
There are several input dry contacts at the X3 slot.
Figure 6
Input dry contacts
3.3.2 Maintenance Bypass Cabinet Interface
J26 and J30 are the MBC interface.
NOTE
When operating the Liebert
®
 NX
 with dry contacts, ESD measures must be taken or the 
contacts may be damaged.
Table 1
Input dry contacts at X3
Position
Name
Description 
J4.1
ENV
3
Battery Room Alarm (Normally Closed)
J4.2
BtG
Battery Ground Fault Detection (Normally Closed)
J4.3
GEN
1,2
Generator Detection (Normally Open)
J4.4
+12V
+12V Power
1 - Must be configured using configuration software before becoming active.
2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%).
3 - Activating this feature turns the battery charger off.
Table 2
Maintenance bypass cabinet interface
Position
Name
Description 
J26.1
T_IT
1
Input transformer over temperature (N.C.)
J26.2
AUX_I
Reserved
J26.3
+12V
+12V Power
J26.4
GND
Power Ground
J30.1
FUSE
Reserved
J30.2
F_FAN
Fan Fail Alarm (N.C.)
J30.3
T_OT
1
Output Transformer Overtemperature (N.C.)
J30.4
AUX_O
Reserved
1
 - Must be configured using configuration software before becoming active.
NOTE
All auxiliary cables of terminal must be double-insulated. The wire must be 600V, 18-16 AWG 
stranded for maximum runs between 82 and 197 feet (25-60m), respectively.
+1
2V
GE
N
Bt
G
EN
V
GN
D
GN
D
+1
2V
AU
X
_I
T_
IT
AU
X
_0
T_
0T
F_
F
A
N
FU
S
E
OL
FB
DR
V
+12V
+12V
+12V
+12V
X3
J4
J26
J30
J10
NOTE: The black square (on each slot indicates Pin 1.