Figure 40 Liebert
®
 NX
 160-200kVA UPS to 49" battery cabinet interconnection
C
C
C
A
A
NX 160-200KVA UPS Module
Front View
49" Battery Cabinet Right-Side Views
B
B
D
D
D
NOTES:
1. All cables must be repositioned prior to and while setting the cabinets in their installed location.
2. Refer to the individual drawing of each piece of equipment for additional details.
Run
From
To
Conductors
A
UPS Battery Terminal Block
External Battery Cabinet
Positive, Negative
B
External Battery Cabinet
Additional External
Battery Cabinet(s)
Positive, Negative
C
Battery Cabinet(s) Breaker
Control Terminal Block
UPS Monitoring Board
Battery Breaker
Auxiliary Contacts
D
UPS Ground
Battery Cabinets Ground
Ground