Emerson 40-200KVA Mode D'Emploi

Page de 132
Operator Control and Display Panel
82
10.3 Control Buttons
The Control Buttons on the front panel may be used to shut down the UPS completely, turn the 
inverter On or Off, restart the UPS after a fault and silence the alarm, as shown in Figure 55. The 
function of each button is described in Table 28.
Figure 55 Location of control buttons
NOTE
To activate a button properly, press and hold until you hear a short beep—about two seconds.
Table 28
Control buttons
Button
Function
EPO
Completely shuts down the UPS, including the static switch.
CAUTION: Use caution before pressing the Emergency Power Off (EPO) button. This button 
completely shuts down the unit and cuts off power to the critical load.
Inverter Off
Press this button to shut down the inverter during operation. The load will be transferred to 
static bypass.
Fault Clear
After the UPS shuts down due to a fault and the alarm condition has been resolved, press 
this button to clear the fault and restart the UPS.
Silence On/Off
Press this button once to silence the alarm buzzer when an alarm is active. Any new fault will 
sound the buzzer again.
If the alarm buzzer is not beeping, press this button to test the alarm sound.
Inverter On
Press this button to start the inverter and transfer from static bypass to inverter.
NOTE: If the inverter is not ready, this will not activate the UPS.
Silence On/Off button
INVER TER  ON
SILENC E ON/ OFF
INVER TER  OFF
FAULT C LEAR
EPO
LED1
LED2
LED3
LED4
LED5
STATUS
F2
F4
HELP
F1
F3
?
L-N current (A)
Frequency (HZ)
L-L voltage (V )
P owerFactor
L1-N/L 2
71. 4
59. 9
480
0. 99
L 2-N/ L3
70.8
59.9
480
0. 99
L 3-N/ L1
71.3
59.9
480
0.99
Output
Input disconnect closed          
01-06 09:15
Bypass abnormal                      
01-06 09 :15
Liebert NX
2007-01-06
09:20:37
S ingle
Normal
80kV A-3X 3
Output disconnect closed        
01-06 09:15
Bypass
Main
Button cover
EPO button
Inverter On button
Inverter Off button
Fault Clear button