Installation
9
2.0
I
NSTALLATION
This section describes the Liebert
®
 APM
’s environmental requirements and mechanical 
considerations that must be taken into account when planning the positioning and cabling of the UPS 
equipment.
Because each site is unique, this section presents a guide to general procedures and practices that 
should be observed by the installing engineer, rather than step-by-step installation instructions.
NOTICE
Risk of improper installation. Can cause equipment damage.
Do not apply electrical power to the UPS equipment before the commissioning engineer 
arrives at the installation site.
The UPS must be installed by a properly trained and qualified engineer in accordance with 
the information contained in this chapter. All the equipment not referred to in this manual is 
shipped with details of its own mechanical and electrical installation information.
!
WARNING
Risk of electric shock. Can cause injury, property damage and death.
Special care should be taken when working with the batteries associated with this equipment. 
When connected together, the nominal battery voltage is 288VDC and is potentially lethal.
• Eye protection should be worn to prevent injury from accidental electrical arcs.
• Remove rings, watches and all metal objects.
• Only use tools with insulated handles.
• Wear rubber gloves.
If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in 
a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with skin, the affected area should be washed immediately 
with large amounts of water.
NOTE
Three-phase, four-wire input power is required.
NOTE
Input power must be supplied to the Liebert APM from a properly grounded Wye or Delta 
source. The Liebert APM is not for use with impedance grounded systems, corner-grounded 
systems or high-leg Delta systems. For these applications, an isolation transformer must be 
installed between the input power and the Liebert APM.