36      Chapter 5  Operating SCU 
ACTURA Flex 48330
 
Power System  User Manual 
4. At any system information page, press “ENT” to enter the “MAIN MENU” page, 
which contains 3 sub-menus: “Status”, “Maintenance” and “Settings”. 
Main Menu               
Status    
Maintenance 
 Settings  
         
 
You can press “
” or “
” repeatedly to select a sub-menu, and press “ENT” to 
enter the sub-menu. Press “ESC” to return to the menu of higher level.   
1) Status   
Including rectifier information, active alarm information and alarm history 
information.  
2) Maintenance   
The maintenance operation can be conducted only when the battery management 
mode is set to “Manual”. The maintenance includes battery FC, BC and test, load 
power off/on, battery power off/on and rectifier voltage trimming, current limit, 
switch control and resetting.   
3) Settings   
Including the setting of alarm parameter, battery parameter, AC/DC parameter, 
rectifier parameter and system parameter. 
5.3  Querying System Status 
5.3.1    First Page Of System Information 
1. At the main menu page, press “ESC” to return to the first system information 
page.  
2. If no operation is conducted on the monitoring module keypad for 8 minutes, the 
LCD will return to the first system information page and shut down the backlight to 
protect the screen. Pressing any key will turn on the back light.   
The first system information page contains the major system operation information, 
including date/time, busbar voltage, total load current, system operation state 
(normal or alarm), battery management mode (AUTO or MANUAL) and battery 
state. 
Among which, the battery state include FC, temperature compensation, BC, Cyclic 
Boost, test, short test and scheduled test. The current time are displayed in two 
pages shifting at the interval of 2s. One page shows year, month and date, the