Emerson 48330 Manuel D’Utilisation

Page de 96
60      Chapter 5  Operating SCU 
ACTURA Flex 48330
 
Power System  User Manual 
5.7.5  Battery Test Parameters 
1. There are 7 related pages, as shown below:   
Battery Test             
Voltage:          45.2 
Time:     300min 
 
 
 
Test End Cap:   
 
0.700C10 
Planned Test:      
N         
 
 
 
Planned Test1:   
  01.02 12Hr 
Planned Test2:   
  04.02 12Hr    
 
 
Planned Test3:   
  07.02 12Hr 
Planned Test4:   
  07.02 12Hr    
 
 
Short Test:     
 
Enable:   Y 
Alarm Current   
                  10A   
 
 
 
Short Test:   
Cyclye:  300h 
Duration:    
                  5min 
 
 
Stable Test 
Enable:            Y 
Current:             
                  9999A 
 
 
Use “
” or “
” to select one page or one of the parameters, and “
” or “
” to 
select the parameter value. Press “ENT” to confirm and save.