Chapter 5  Operating SCU      65 
ACTURA Flex 48330
 
Power System  User Manual 
5.7.9  Rect Settings 
1. There are three related pages, as shown below:   
Rect Over Volt: 
            59.0V 
Default Volt:       
            42.0V       
 
 
 
Walk-in Enabled 
 
              N 
Walk-in Time:    
            8s             
 
 
 
Fan Speed     
 
            Full Speed 
HVSD Time:             
      300s     
 
 
 
Use “
” or “
” to select one page or one of the parameters, and “
” or “
” to 
select the parameter value. Press “ENT” to confirm and save. 
2. The value description of the parameters is listed below: 
Table 5-17    Value description of rectifier settings 
Parameter  
Range 
Default 
Value description   
Rect Over Volt  56V ~ 59V  59V 
The rectifier over voltage alarm will be 
raised when the rectifier output voltage is 
higher than the “Rect Over Volt”   
Default Volt 
48V ~ 58V  53.5V 
 
The “Default Volt” must be 
lower than the “Rect Over Volt” 
Walkin Enabled  Y, N 
Walkin Time 
8s ~ 128s 
10s 
The output soft start function means the rectifier voltage will rise from 0V 
to the “Default Volt” after the “Walkin Time”     
Fan Speed 
Full Speed, 
Half Speed 
Half 
speed 
When set to “Half Speed”, the rectifier will regulate the fan speed 
according to the temperature. When set to “Full Speed”, the fan will 
operate at full speed   
HVSD Time 
50s ~ 300s  300s 
The rectifier will shut off automatically upon over-voltage, and restart after 
a certain delay to see whether it is still over-voltage then. That delay is set 
through the parameter “HVSD Time”. If the rectifier’s output voltage is 
normal within the delay, the rectifier is regarded normal; otherwise, the 
rectifier will be locked out and auto-restart function will be disabled