Emerson 48330 Manuel D’Utilisation

Page de 96
68      Chapter 5  Operating SCU 
ACTURA Flex 48330
 
Power System  User Manual 
Table 5-18    Value description of system settings 
Parameter  
Range  
Default
Value description   
Text 
Chinese, English and 
Spanish 
Chinese Set according to your need   
Address 
1 ~ 254 
 
The addresses of power systems that are at the 
same monitored office should be different   
CommMode 
modem, EEM-M, 
RS-232 
 
“MODEM”: Through modem and based on the 
Telecom protocol.   
“EEM-M”: Through modem and based on the EES 
protocol.  
“RS-232”: Through a transparent serial port and 
based on the Telecom protocol     
BaudRate 
1200bps, 2400bps, 
4800bps, 9600bps 
 
Make sure the baud rates of both the sending and 
receiving parties are the same   
CallBack 
Num. 
1 ~ 10 
When 
“CommMode
” is set to 
“MODEM” or 
“EEM-M”  
CallBack 
Number 
19 digits at most 
 
Set according to the actual need. In a extension 
system, sometimes you need to put a “,” between the 
main number and extension number. When the 
callback number is less than 19 digits, end it with a 
“#”  
Set Date 
2,000 ~ 2,099 
 
Set Time 
Hour, min, sec 
 
Set the time according to the current actual time, 
regardless of whether it is a leap year or not   
Initialize 
password 
Y, N 
Selecting “Y” can reset the user level and 
administrator level passwords to the defaults   
 
 
 
Operator 
level or 
above 
 
 
 
Init Param 
(Initialize 
parameter
s) 
Y, N 
When the system parameters cannot be set normally, 
and the usual resetting methods do not work, you 
can set the “Init Param” to Y, and all the system 
parameters will be restored to defaults. Alarms may 
be raised for the defaults may fail to meet the actual 
situation. Set the parameters according to the actual 
situation then.