Installation Drawings
62
Figure 39 Outline drawing, Liebert BDC for Liebert
®
 APM
, 15-45kVA
Figure 40 Outline drawing, Liebert BDC for Liebert APM, 15-90kVA
6.3" (159)
Outside Panel
Cable Entry Area
11.4" x 13.2"
(290 x 335mm)
Cable Entry Area
11.4" x 13.2"
(290 x 335mm)
6.5" (164)
Outside Panel
6.7" (169)
Outside Panel
6.4" (162)
Outside Panel
23.7"
(602)
34.6"
(879mm)
28.3"
(719)
Bracket
Centers
5.5" (140)
23.6" (600)
Center
of
Gravity
Leveling
Feet
RIGHT SIDE
UAM06008
Rev. 4
FRONT
78.7"
(2000mm)
TOP
Maximum Door
Swing: 120°
NOTES
1. All dimensions are in inches [mm].
2. 24" (610mm) minimum clearance above unit and
    36" (914mm) front access required for service.
3. Keep cabinet within 15° of vertical.
4. Top and bottom cable entryavailable through removable
    access plates. Remove, punch to suit conduit size and replace.
5. Control wiring and power wiring must be run
    in separate conduits.
6. Copper cables only are recommended.
7. All wiring is to be in accordance with national
    and local electrical codes.
BOTTOM
X
Z
39.5" (1000)
24" (609)
Liebert BDC
with Distribution Type
Dimension, in. (mm)
Weight,*
lb (kg)
X
Y
Z
Without Panelboard
11.8" (300)
39.4" 
(1000)
14.9" (379)
525 (239)
With Panelboard
11.8" (300)
39.4" 
(1000)
14.9" (379)
625 (284)
* Shipping weight, add 150lb. (68kg)
6.3" (159)
Outside Panel
Cable Entry Area
11.4" x 13.2"
(290 x 335mm)
Cable Entry Area
11.4" x 13.2"
(290 x 335mm)
6.5" (164)
Outside Panel
6.7" (169)
Outside Panel
6.4" (162)
Outside Panel
23.7"
(602)
34.6"
(879mm)
28.3"
(719)
Bracket
Centers
5.5" (140)
23.6" (600)
24" (609)
X
Y
Center
of
Gravity
Leveling
Feet
UAM06010
Rev. 4
BOTTOM
RIGHT SIDE
FRONT
78.7"
(2000mm)
TOP
Maximum Door
Swing: 120°
z
39.5" (1000)
NOTES
1. All dimensions are in inches [mm].
2. 24" (610mm) minimum clearance above unit and
    36" (914mm) front access required for service.
3. Keep cabinet within 15° of vertical.
4. Top and bottom cable entry available through
    removable access plates. Remove, punch to
    suit conduit size and replace.
5. Control wiring and power wiring must be run
    in separate conduits.
6. Copper cables only are recommended.
7. All wiring is to be in accordance with national
    and local electrical codes.
Liebert BDC with Distribution Type
Dimension, in.  (mm)
Weight,* lb (kg)
X
Y
Z
No Distribution
11.8" (300)
39.4" (1000)
14.9" (379)
550 (250)
With 2-225A Subfeed Breakers
11.8" (300)
39.4" (1000)
14.9" (379)
660 (300)
With 400A Panelboard
11.8" (300)
39.4" (1000)
14.9" (379)
660 (300)
* Shipping weight, add 150lb. (68kg)
No Distribution With 480V Transformer
11 8" (300)
32 7" (830)
24 8" (630)
1522 (692)