UPS Alarm and Status Messages
43
A
PPENDIX
A - UPS  A
LARM
 
AND
 S
TATUS
 M
ESSAGES
Table 7 shows alarm and status messages as they appear in Liebert NXL’s touchscreen and in the 
history log, along with a description and recommended actions, if any.
If the recommended action fails to correct the condition, contact your factory-authorized service pro-
vider.
The “Service Telephone Number” can be found by pressing “CONFIG,” “Ratings,” “More>>” on the 
menu bar.
Table 7
Liebert NXL alarm and status messages
Event Message
Event Definition
Recommended Action
Auto Restart Fail
An Automatic Restart was enabled but has failed 
to complete.
With Automatic Restart enabled, the unit 
automatically restarts after an End of Discharge 
(EOD) event. This alarm means that one of the 
auto restart requirements was true, but failed 
before the restart sequence completed.
For example, one conditional requirement for 
Automatic Restart to occur is that the Rectifier 
Input Voltage must be within acceptable limits. If, 
during the restart sequence, the input voltage 
drops out of tolerance, the Automatic Restart will 
fail.
This alarm is self-clearing. When the condition is 
no longer present, the alarm and any control 
activity tied to the alarm reverts to normal.
Press “SILENCE” to silence the audible alarm.
Check the active events to determine the status of 
the UPS.
If “Auto Restart Fail” is the only alarm present, 
attempt a manual start of the unit by pressing 
“Startup,” “Manual Start,” then following the prompts 
to attempt to place the unit back online.
If the manual start fails, or if there are other alarms 
present that won’t clear, contact your factory-
authorized service provider.
Auto Rexfer Failed
The condition that caused an automatic transfer 
to bypass failed to clear within a specified time 
delay.
An example of a recoverable transfer (one which 
the controls may attempt to recover from 
automatically) is an overload that exceeded the 
overload time curve.
Press “SILENCE” to silence the audible alarm.
Press “RESET” to attempt to clear active events. 
This does not clear the “Auto Retransfer Failed” 
alarm.
If all other alarm conditions clear, attempt a manual 
transfer back to Inverter by pressing “Transfer,” 
“UPS.”
If the transfer is successful, press “RESET” to clear 
this alarm from the Active Event Window. If the UPS 
fails to transfer and the active messages do not 
explain the reason, contact your factory-authorized 
service provider.
Batt CB “#” Open
Battery Circuit Breaker “#” is open.
This status message is self-clearing. When the 
condition is no longer present, the message and 
any control activity tied to the status event reverts 
to normal. (The Liebert NXL has eight battery 
circuit breakers.)
Press “SILENCE” to silence the audible alarm.
Check the status of Battery Circuit Breaker “#”. If it 
is open, the alarm is normal.
If Battery Circuit Breaker “#” is closed, contact your 
factory-authorized service provider.