Operation of the HELP key: 
1. Only at the primary screen can you use the HELP key to display the help screen.   
2. The HELP key is invalid at the start screen.   
3. At the default screen, help screen, or when the LCD backlight is off, the primary screen will return if you press the 
HELP key. 
4.3   Prompt Window 
A prompt window is displayed during the operation of the system to alert you to certain conditions and/or to require 
your confirmation of a command. The prompts are provided in Table 4-7.   
Table 4-7    Prompts and meanings 
No. 
Prompt 
Meaning 
Transfer with interrupt, confirm or 
cancel 
Inverter and Bypass supplies are not synchronized and any load transfer 
between the supplies will cause a brief load interruption 
The load is too high to be 
transferred with interrupt 
The total load must be less than the capacity of one unit to allow a parallel 
system to perform an interrupted transfer from bypass to inverter 
This operation leads to output 
shutdown, confirm or cancel     
No alternative supply is available and any Inverter Off operation will cause the 
load to be de-energised 
This operation leads to inverter 
overload, confirm or cancel 
Turning off this inverter will lead to the overload of remaining inverter(s) in a 
parallel system 
Turn on more UPS to carry current 
load 
The number of paralleled inverters already turned on is insufficient to carry the 
existing load 
Battery will be depleted, confirm or 
cancel 
Battery capacity test discharges the battery 100%. This prompt apears to 
require your confirmation. Cancelling the test will ends the test and transfers the 
UPS to Normal mode 
System selftest finished, everything 
is ok 
No action required 
System selftest finished, please 
check the current warnings 
Check the current record window 
Enter control password       
Required for battery or UPS test (default: 12345) 
10 
Battery selftest condition is low, 
please check battery state and 
loadlevel 
Battery test condition is not met. Please check whether the battery is in boost 
charge state and the load level meet the battery test conditions. To initiate the 
battery test, the load must range between 20% and 80% 
11 
Freshening charge condition is low, 
please check battery settings and 
state 
This prompt appears when you select the freshening charge command while 
the freshening charge condition is not met (such as no battery, charger failure)