Chapter 6  Battery      49 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
[
 BCB: 
A BCB is generally installed in an enclosure on the wall close to the battery installation. The connection of BCB box 
available for the HIPULSE U UPS is described in the following section. 
 
Figure 6-1    Battery room design 
6.9   BCB Box (Optional) 
The battery circuit breaker (BCB) box of 160/200kVA UPS adopts wall mounting, while that of the 300/400kVA UPS 
can adopt both wall mounting and floor mounting. The installation hole dimensions are shown in Figures 6-2 to 6-4. 
455
73
8
 
Figure 6-2    Installation hole dimensions for wall mounting of BCB box of 160/200kVA UPS (unit: mm) 
1042
654
 
Figure 6-3    Installation hole dimensions for wall mounting of BCB box of 300/400kVA UPS    (unit: mm)