Site Planning Data, Liebert Npower: 30-130kVA, 60 Hz, 208 or 480VAC
UPS
Rating
Voltage
Standard AC Input
AC Input w/Filter Opt.
Battery
AC Output
Mechanical Data
Current (A)
Rec.
OCPD
Current (A)
Rec.
OCPD
Nom.
VDC
Battery
kW
Max.
Discharge
Current
Dimensions
WxDxH, in. (mm)
Weight
lb. (kg)
Floor Loading
lb./ft
2
 (kg/m
2
)
Heat Dis.
BTU/h (kWH)
Cooling Air
CFM (m
3
/h)
kVA
kW
Input
Output Nom.
Max.
Nom.
Max.
Nom
OCPD
30
24
208
208
92
114
150
80
99
125
480
26
66A
83
125
31.7x32.5x71
(805x825x1800)
2100 (953)
294 (1435)
8,500 (
2.5
)
720 
(1223)
30
24
480
208
38
48
60
33
41
50
480
26
66A
83
125
1850 (839)
259 (1265)
7,500 (2.2)
30
24
480
480
38
48
60
33
41
50
480
26
66A
36
50
259 (1265)
7,500 (2.2)
40
32
208
208
122
153
200
106
133
175
480
34
88A
111
150
31.7x32.5x71
(805x825x1800)
2200 (998)
307 (1499)
11,000 (
(3.2)
720 
(1223)
40
32
480
208
51
64
80
44
55
70
480
34
88A
111
150
1900 (862)
266 (1299)
10,000 (2.9)
40
32
480
480
51
64
80
44
55
70
480
34
88A
48
60
266 (1299)
10,000 (2.9)
50
40
208
208
153
191
250
133
166
200
480
43
109A
139
175
31.7x32.5x71
(805x825x1800)
2200 (998)
307 (1499)
14,000 
(4.1)
720 
(1223)
50
40
480
208
64
80
100
55
69
100
480
43
109A
139
175
1900 (862)
266 (1299)
12,000 (3.5)
50
40
480
480
64
80
100
55
69
100
480
43
109A
60
80
266 (1299)
12,000 (3.5)
65
52
208
208
193
242
300
171
213
300
480
55
141A
180
225
39.4x32.5x71
(1001x825x1800)
2500 (1134) 281 (1372)
18,000 
(5.3)
960 
(1631)
65
52
480
208
80
99
125
70
88
125
480
55
141A
180
225
2150 (975)
242 (1182)
15,000 (4.4)
65
52
480
480
80
99
125
70
88
125
480
55
141A
78
10
242 (1182)
15,000 (4.4)
80
64
208
208
238
298
400
210
262
350
480
68
174A
222
300
39.4x32.5x71
(1001x825x1800)
2500 (1134) 281 (1372)
22,000 
(6.4)
960 
(1631)
80
64
480
208
98
122
150
87
108
150
480
68
174A
222
300
2150 (975)
242 (1182)
18,000 
(5.3)
80
64
480
480
98
122
150
87
108
150
480
68
174A
96
125
242 (1182)
18,000 
(5.3)
100
80
208
208
296
370
450
261
326
400
480
85
218A
278
350
49.2x32.5x71
(1250x825x1800)
3350 (1520) 302 (1474)
26,000 
(7.6)
)
1440 
(2447
100
80
480
208
122
152
200
108
135
175
480
85
218A
278
350
2800 (1270)
252 (1230)
21,000 (6.1)
100
80
480
480
122
152
200
108
135
175
480
85
218A
120
150
252 (1230)
21,000 (6.1)
130
104
208
208
385
481
600
336
420
500
480
111
283A
361
450
49.2x32.5x71
(1250x825x1800)
3350 (1520) 302 (1474)
33,000 
(9.7)
1440 
(2447)
130
104
480
208
158
198
250
140
175
225
480
111
283A
361
450
2800 (1270)
252 (1230)
27,000 (7.9)
130
104
480
480
158
198
250
140
175
225
480
111
283A
156
200
252 (1230)
27,000 (7.9)
1
2,3,8,12 6,14
1
2,3,8,12
6
4
1,3,5,8,12 1,3,8,12
6
13
13, 14
Notes for Table
1.
Nominal (Nom) current is based on full rated output load.
2.
Maximum (Max) current (125% of nominal) is short duration for battery recharge 
conditions.
3.
UPS input and bypass cables must be run in separate conduit from output cables.
4.
Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
5.
Power cables from UPS DC link to batteries should be sized for a total maximum 2.0V line 
drop (measured at the UPS) at maximum discharge current.
6.
OCPD=Overcurrent Protection Device. Recommended AC input and AC output overcurrent 
protection represents 125% of nominal full load current (continuous) per NEC 215.
7.
Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground 
conductors are recommended. Neutral conductors to be sized for full capacity per 
NEC 310-15(b)(4). References are per NEC 1999.
8.
Wiring requirements: 
AC Input and Output: 3-phase, 3- or-4-wire plus ground, depending on UPS configuration. 
See Installation Manual and submittal drawings for specific instructions. 
DC Input: 2-wire (positive and negative), plus ground.
9.
All wiring is to be in accordance with national and local electrical codes.
10. Minimum access clearance is 3 ft. (0.9m) front and 1 ft. (0.3m) above UPS.
11. Top or bottom cable entry through removable access plates. Punch plate to suit conduit 
size, then replace.
12. Control wiring and power wiring must be run in separate conduit.
13. Weights and dimensions shown do not include battery cabinet, Slim-Line distribution 
cabinet or other options.
14. Add 560 lb. (254kg) for 100-130kVA unit with dual input and isolated 208VAC output.
15. Backup emergency generator must be properly sized and equipped with an isochronous 
governor (generator frequency regulation) and a UPS-compatible voltage regulator.
16. An on-site automatic transfer switch should be equipped with auxiliary contacts for UPS 
“on generator” current limit. Refer to Liebert publication 91K-PLT-48-02.
17. An external isolated maintenance bypass circuit might cause utility AC input to be out of 
phase with the UPS AC output.
© 2004 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names 
referred to are trademarks or registered trademarks of their respective owners.
SL-24531 (11/04) Rev. 4
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com