Installation
8
2.0
I
NSTALLATION
2.1
Inspection
Upon receiving the UPS, examine the packaging for any signs of mishandling or damage. If any dam-
age is noted, call your local dealer or Liebert representative and/or notify your carrier.
2.1.1 Environment
2.1.2 Required Setup Equipment
The tools below are required to properly set up your UPS:
• Pallet jack
• 1/2" (13mm) ratchet or wrench
• Torque wrench (in-lb)
• Flathead screwdriver
• #2 Phillips screwdriver
2.1.3 Site Preparation
When deciding where to locate your UPS, 
consider the weight and size of the unit. Make 
sure that the structural integrity of the floor 
can withstand the weight of a fully loaded unit.
Check to make sure that your UPS will be 
located in a well-ventilated area with at least 
12 inches (305mm) behind it. The UPS is 
air-cooled utilizing internal fans. Air is drawn 
into the front of the UPS and is exhausted 
through ventilation grilles in the back. It should 
also have at least 36 inches (915mm) in front in 
order to change modules when necessary.
The unit frame is bolted to the shipping pallet to ensure safety. It is recommended that a pallet jack 
be used to transport the unit to its operating location (prior to unbolting the unit).
NOTE
Operating in temperatures above 77°F (25°C) will reduce battery life. The UPS environment 
must be free of conductive contaminants and excessive moisture (water and condensation), 
flammable vapors, chemical fumes, corrosive gases and liquids.
36"
(915 mm)
12" 
(305mm)