Emerson 208 Manuel D’Utilisation

Page de 44
Operating Instructions
19
3.4
Operating Procedures
3.4.1 Start-Up and Initialization
Follow these steps to start up the UPS.
1. Ensure the manual bypass switch is in 
UPS position. Close Input Circuit Breaker 
(CB1) and close the Control Enable 
Switch (SW2). You should see the 
following on the LCD display window:
2. Press  
or   
button. 
3. Press 
 
to access the Main Menu.
3.4.2 Shutting Down the UPS
Use the following procedure to power down 
the UPS.
1. Press 
 to disable power from the 
connected equipment. 
2. Verify request to disable the output by 
pressing .
3. Turn off the Enable Switch (SW2). Open 
the Input Circuit Breaker (CB1).
3.4.3 Manual Transfer to Bypass
To manually transfer the UPS to bypass, 
move the manual bypass switch to the bypass 
position. The manual bypass switch is behind 
the front bottom bezel. To transfer the UPS 
from bypass to normal mode, follow the on-
screen instructions.
Once 
 is pressed, the bypass alarm will 
annunciate and cannot be canceled until the 
manual bypass switch is operated.
To transfer the UPS from bypass to normal 
mode, simply operate the manual bypass 
switch back to the UPS position.
On return from bypass, the following screen 
will be displayed.
UPS Initializing
Please wait . . .
*Press
to Enable
UPS Output.
ESC
On Mains/Utility
Output % = xx
Battery Minutes yyy
Press
for menu 
NOTE
The load is not protected from utility 
interruptions when the UPS is in 
bypass mode.
Main Menu
> Transfer to Bypass
Transfer to Bypass
Press
for bypass
Press ESC to cancel
Assert manual bypass
Manual 
Bypass 
Switch
On UPS
On Bypass
UPS on manual bypass
No active alarms
See Event Log